REFRIGERANT PIPING
WARNING
If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a fan heater, cooking stove or heating
unit, noxious gas may be generated.
Permissible pipe length and permissible height difference
The length of a connection pipe to the indoor unit should be 164' (50 m) or less.
For details, refer to the installation manual attached to the outdoor unit.
REQUIREMENT
When the refrigerant pipe is long, set the support brackets to fix the pipe at intervals of 8.9' to 9.8' (2.5 to 3 m).
If the pipe is not fixed, noise may be generated.
Piping dimensions
Outdoor unit
Outdoor unit
Single Indoor unit connection
Multi indoor unit connection
FS unit
FS unit
indoor unit
indoor unit
(2)
(1)
(1)
(2)
(4) (3)
(4)
(2)
(2)
(3)
They vary depending on the outdoor unit. For details, refer to the Installation Manual attached to the outdoor unit.
Outdoor unit side pipe size (1)
Flow Selector unit
RBM-
Y0384FUL
Y0614FUL
Y0964FUL
Total capacity codes of indoor units at the downstream side
(kBTU/h)
Below 38
38 to below 61 61 to 96 or less
Outdoor unit side pipe size (mm)
Suction gas pipe
Ø5/8"
Ø5/8"
Ø7/8"
Discharge gas pipe
Ø1/2"
Ø1/2"
Ø3/4"
Liquid pipe
Ø3/8"
Ø3/8"
Ø1/2"
Indoor unit side pipe size (2)
Capacity rank
Length of piping
Gas side
Liquid side
007 to 012
49 ft (15 m) or less real length
Ø3/8"
Ø1/4"
Exceeds 49 ft (15 m) real length
Ø1/2"
Ø3/8"
015 to 018
49 ft (15 m) or less real length
Ø1/2"
Ø1/4"
Exceeds 49 ft (15 m) real length
Ø5/8"
Ø3/8"
021 to 054
-
Ø5/8"
Ø3/8"
072 to 096
-
Ø7/8"
Ø1/2"
Indoor unit side pipe size (3)
Total capacity codes of indoor units
at the downstream side
Suction gas side
Liquid side
Below 61
Ø5/8"
Ø3/8"
61 to 96 or less
Ø7/8"
Ø1/2"
Y-shaped branching joint (4)
Total capacity codes of indoor units
at the downstream side
Y-shaped branching joint
Below 61
RBM-BY55UL
61 to 96 or less
RBM-BY105UL