Page 1: ...Installation Manual PMV Kit RBM PMV0363E RBM PMV0903E EB99802801 1 Installation Manual PMV Kit English ...

Page 2: ...e customer to keep the Installation Manual together with the Owner s Manual CAUTION New Refrigerant Air Conditioner Installation THIS PMV KIT ADOPTS THE NEW HFC REFRIGERANT R410A WHICH DOES NOT DESTROY OZONE LAYER The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Accompanied with the ...

Page 3: ...cause electric shock Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas If a combustible gas leaks and stays around the unit a fire may occur CAUTION Tighten flare nuts using a torque wrench according to the specified method If the flare nuts are tightened too much they may later break and cause refrigerant leak EN 3 EN 4 2 INSTALLATION OF NEW REFRI...

Page 4: ...here oil including machine oil steam oil smoke or corrosive gas generates Place where a device generating high frequency inverter non utility generator medical apparatus or communication equipment is set A bad influence may generate by malfunction of the air conditioner control error or noise for such equipment EN 5 EN 6 Installation space Make space for installation and service Make space to the ...

Page 5: ...efrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire source such as a fan heater cooking stove or heating unit noxious gas may be generated Allowable length of refrigerant piping PMV Kit Indoor unit PMV Kit Indoor unit Refrigerant pipe 2 m to 10 m Indoor unit PMV Kit NO GOOD OK Label Attached joint Attached joint Model name RBM PMV0363E RBM PMV0903E Indoor unit...

Page 6: ...pipe connecting work of the indoor unit Refer to the following table for tightening torque REQUIREMENT If an excessive torque is applied the nut may crack depending on the installation conditions Airtight test Air purge etc For airtight test air purge addition of refrigerant and gas leak check follow the Installation Manual attached to the outdoor unit REQUIREMENT Be sure to use the tool such as c...

Page 7: ...nd and vibration 7 ELECTRIC WORK WARNING 1 Using the specified wires ensure to connect the wires and fix wires securely so that the external strength of the wires do not transmit to the connecting part of the terminals Incomplete connection or fixation may cause fire etc 2 For electric work strictly follow to the Local Regulation in each country and the Installation Manual and use an exclusive cir...

Page 8: ...g method Remove the connector conversion cable mounted to the connection cable out of the PMV kit main body and then connect it The connector conversion cable and the additional clamp filter are used Indoor unit except above indoor units Work procedure 1 In case of indoor unit which connector conversion cable is not used but the additional clamp filter is used Applicable model High wall type 4MH 2...

Page 9: ... indoor unit which the connector conversion cable is not used but the additional clamp filter is used Applicable model High Wall type 3H series For 3H series models which have E1 at the end of each model name the works 1 and 2 are unnecessary Procedure 1 2 and 3 are same to the Work procedure those in Work procedure 1 4 After turning off the power supply remove the terminal cover and the clamp bas...

Page 10: ...it Indoor unit CN82 connector Connector conversion cable Indoor control P C board Connection cable PMV lead wires Clamp filter Formerly attached Additional clamp filter Accessory Pulse motor valve PMV Indoor unit side 6 Using binding band put together the removed PMV lead wires and then store in the electrical parts box 7 Process the wiring work and then close the electrical parts box SW11 1 ON 2 ...

Page 11: ......

Page 12: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN EB99802801 1 ...