Terminal DI1 / DI1: Safety contact (Normal close)
MODE 1 (Normally close, DC12 V) *When Bit1 of SW505 is OFF
• If this contact is open for more than 1 minute, the check code P10 is generated and the Dx-coil controller switches off
automatically.
MODE 2 (Normally open, DC12 V) *When Bit1 of SW505 is ON
• If this contact is short for more than 1 minute, the check code P10 is generated and the Dx-coil controller switches off
automatically.
SW701
SW505
SW701
SW505
SW701
SW505
SW701
SW505
SW701
SW505
Function
OFF
OFF
The coil drive voltage is input to the relay arranged locally for DI1, and judge that the close is
positive. (Default)
Relay: Local arrangement
ON
The coil drive voltage is not input to the relay arranged locally for DI1, and judge that the open is
positive.
Relay: Local arrangement
ON
OFF
For DI1, short-circuit the (+) signal voltage and DI1 (-) GND with a SW or harness, and judge
that the close is positive.
Relay: Not required
* The signal voltage is DC12 V ± 10%, and it is necessary to add a SW element to the signal line.
ON
For DI1, open the (+) signal voltage and DI1 (-) GND, and judge that the open is positive.
Relay: Not required
* The signal voltage is DC12 V ± 10%, and it is necessary to add a SW element to the signal line.
SW505
1
OFF
ON
1
2
4
3
Bit1:
OFF
OFF
ON
1
OFF
ON
1
2
4
3
Bit1:
OFF
OFF
ON
DI1
DI1
MAX. 1 m
Locally procured
GND
Normally
closed
SIGNAL (12 V)
DI1
DI1
MAX. 1 m
Locally procured
SIGNAL (+)
Signal Voltage (DC12 V ± 10%)
SIGNAL (-)
GND
Normally closed
(+)
(-)
1
OFF
ON
1
2
4
3
Bit1:
ON
OFF
ON
1
OFF
ON
1
2
4
3
Bit1:
ON
OFF
ON
DI1
DI1
MAX. 1 m
Locally procured
GND
Normally
open
SIGNAL (12 V)
DI1
DI1
DI1
MAX. 1 m
Locally procured
SIGNAL (+)
Signal Voltage (DC12 V ± 10%)
SIGNAL (-)
GND
Normally open
(+)
(-)
29-EN