background image

– 30 –

EN

Installation Manual

7. DN setting

Perform the advanced settings for the air conditioner.
Carry out the setting operation while the indoor unit is stopped. (Turn off the air conditioning unit before starting the 
setting operation.)

NOTE

• The following changes are settings to be configured by installation and service personnel.

If they are set incorrectly, trouble such as the product becoming inoperable may occur.

• For indoor units which do not support the functions below, the following DN code settings may not be possible.
• Do not perform header/follower connection for a remote controller which does not support the functions below.
• For operation when connected to an air conditioning control system which does not support the functions below, refer 

to “Changing the temperature” in the Owner's Manual.

1

Push the [

 

 ] / [

 

 ] button to select 

“7. DN setting” on the “Field setting menu” 
screen, then push the “

 Set” [

 

F2] button.

The fan and louver of the indoor unit operate. 
When the group control is used, the fan and 
louver of the selected indoor unit operate.

Move the cursor to select “Code(DN)” with the 

 

” [   F1] button, then set 

“Code(DN)” with the [ 

 

 

] / [ 

 

 ] 

button.

Move the cursor to select “Data” with the 

 

” [ 

 F2] button, then set “Data” 

with the [ 

 

 

] / [ 

 

 ] button.

2

Refer to the Installation Manual supplied 
with the indoor unit or service manual for 
details about the Code(DN) and Data.

3

Push the [

 

 MENU] button to set the other 

Code(DN) and Data. After “Continue?” is 
displayed on the screen, push the 

 

Yes”  [

 

F1] button.

4

Push the “

 

No” [

 

 F2]  button to 

finish the setting operation. “

 

Setting” 

appears on the screen for a while, then the 
screen returns to the “Field setting menu” 
screen.

Pushing the “

 

No” [ 

 F2] button 

displays the unit selection screen when the 
group control is used. Push the [ 

 CANCEL] 

button on the unit selection screen to finish the 
setting operation. “  Setting” appears on the 
screen for a while, then the screen returns to the 
“Field setting menu” screen.

DN

Item

Description

Factory default

77

Dual set point setting

0000: Normal automatic
0002: Dual automatic

0000

DN setting

Code

(DN)

Data

Return

10

0000

Fix

<

>

Set

<

>

Yes

No

No

DN setting

Code

(DN)

Data

Return

10

0001

Fix

<

>

Return

Continue?

No

Yes

DN setting

Summary of Contents for RBC-AMS54E

Page 1: ... manual before using the RBC AMS54E ES RBC AMS54E EN remote controller Refer to the Installation Manual supplied with the indoor unit for any installation instructions other than operations of the remote controller Wired Remote Controller Installation Manual ...

Page 2: ...ents for installing two remote controllers 7 For first use 9 Note 9 Part Names and Functions 10 Monitor screen 11 Initial setting 12 1 Clock 12 2 Name of room 13 3 Screen contrast 14 4 Backlight 15 5 Key lock 16 6 Header Follower 17 7 Language 18 8 Press hold 4sec 19 Field setting menu 20 1 Test mode 20 2 Register service info 22 3 Alarm history 26 4 Monitor function 27 5 Setting louver position 2...

Page 3: ...urns electric shock and other injuries which do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indic...

Page 4: ... 3 Installation Manual Accessory Parts No Part name Quantity 1 Screws M4 x 20 2 2 Wood screws M3 8 x 16 2 3 Owner s Manual 1 4 Installation Manual This manual 1 5 CD ROM 1 ...

Page 5: ...posed to direct sunlight or direct outside air such as the side of a window Do not install the remote controller in a place behind something or to the rear side of an object where air flow is not sufficient Do not install the remote controller in a freezing box or refrigerator as the remote controller is not waterproof Install the remote controller vertically to the wall Installation dimension Roo...

Page 6: ... and 2 Wiring type VCTF 0 5 mm2 to 2 0 mm2 x 2 Total length of remote control wiring and inter wiring between indoor units L L1 L2 Ln 1 remote controller 2 remote controllers 2 remote controllers including a wireless remote controller Up to 500 m Up to 300 m Up to 400 m Total length of inter wiring between indoor units L1 L2 Ln Up to 200 m Indoor unit Indoor unit Indoor unit Indoor unit Remote con...

Page 7: ... screws 2 pieces supplied with the remote controller to attach the rear case of the remote controller to the wall Do not use an electrical screwdriver Do not over tighten the screw Tightening torque is up to 2 kg f cm otherwise the rear case may be damaged 3 Connect the electrical wire from the indoor unit to the terminal block of remote controller Refer to Wire the remote controller Check the ter...

Page 8: ... remote controller Set from 6 Header Follower in Initial setting on the MENU screen For details refer to the page 17 Install the remote controllers For the dual remote controller system install the remote controllers as follows 1 Set one remote controller as the Header remote controller The remote controllers are set as Header remote controller as factory default 2 When the dual remote controller ...

Page 9: ...e controller Follower Sold separately Terminal block for the remote control wiring Earth Indoor unit A B A B A B Remote control wiring Locally procured 0 5 mm2 to 2 0 mm2 Remotecontroller Header Remote controller Follower Sold separately Terminal block for the remote control wiring Earth Indoor unit A B A B A B Remote controller inter unit wires for group control Locally procured Remotecontroller ...

Page 10: ...bout 5 minutes before the remote controller becomes operable When the power is turned on from the second time It takes about 1 minute before the remote controller becomes operable Note For the operation of switching the room temperature sensor or the settings of the test operation refer to the page 20 Power on flashes disappears Remote controller becomes operable About 5 minutes Power on flashes d...

Page 11: ...NCEL button Functions as indicated on the screen such as returning to the previous menu screen 4 button During normal operation adjusts the temperature On the menu screen selects a menu item 5 button During normal operation adjusts the temperature On the menu screen selects a menu item 6 F1 button Varies its function according to the setting screen 7 F2 button Varies its function according to the ...

Page 12: ...ation is performed for 60 seconds 1 Push MONITOR button The monitor screen appears 2 Push CANCEL button to return 1 Displays the set temperature 2 Displays the temperature measured by the indoor temperature sensor of the indoor unit If the sensor is set to that of the remote controller the temperature measured by the remote controller sensor is displayed 3 Displays the temperature around the vent ...

Page 13: ...layed 5 Push the CANCEL button to return The screen returns to the Initial setting screen 1 Push the button to select 1 Clock on the Initial setting screen then push the Set F2 button 2 Push the button to select the Year Month Day and time Push the F1 F2 button to set the value 3 Push the MENU button Initial setting 1 2 1 Clock 2 Name of room 3 Screen contrast 4 Backlight 5 Key lock Set Return Set...

Page 14: ...her cause NOTE The available date range is from January 1st 2016 to December 31st 2099 1 Push the button to select 2 Name of room on the Initial setting screen then push the Set F2 button 2 Set the name of the remote controller Enter the characters of the name in the screen 1 Move the cursor to select the character with the button and F1 F2 button the selected character is highlighted then push th...

Page 15: ...l setting screen then push the Set F2 button 2 Push the F1 F2 button to adjust 3 Push the MENU button The screen returns to the Initial setting screen Return Set Fix ABCDE FGH I J KLMNO PQRST UVWXY Z abcde f g h i j klmno p q r s t uvwxy z 12345 67890 Bedroo Del Return Set Del ABCDE FGH I J KLMNO PQRST UVWXY Z abcde f g h i j klmno p q r s t uvwxy z 12345 67890 705A Fix Initial setting 1 2 1 Clock...

Page 16: ... the MENU button When ON is selected the back light is turned on during operating with the remote controller When OFF is selected the back light is not turned on NOTE The back light of the LCD is turned on as factory default The back light is on for a predetermined time after button operation Initial setting 1 2 1 Clock 2 Name of room 3 Screen contrast 4 Backlight 5 Key lock Set Return Set Backlig...

Page 17: ...nlock 4 Push the MENU button When Lock is selected the key cannot be used during key lock When Unlock is selected the key can be used even during key lock All keys are unlocked while Check is displayed For the key lock setting refer to the owner s manual The factory default is Lock Initial setting 1 2 1 Clock 2 Name of room 3 Screen contrast 4 Backlight 5 Key lock Set Return Set ON OFF Set temp Lo...

Page 18: ...remote controller Schedule timer Off reminder timer Night operation Energy saving operation Return back Saving operation NOTE Some functions are not available when the remote controller is set as the Follower remote controller In the dual remote controller system the latter operation overrides the former The remote controller is set as Header remote controller as factory default If the Header Foll...

Page 19: ...ge The factory default is English These two screens appear for RBC AMS54E ES These two screens appear for RBC AMS54E EN Initial setting 2 2 6 Header Follower 7 Language 8 Press hold 4 sec Set Return Set Language 1 2 English French German Spanish Portuguese Français Deutsch Español Português Return Fix Language 2 2 Dutch Return Fix Nederlands Language 1 2 English Italian Greek Russian Turkish Retur...

Page 20: ...2 button 2 Push the button to select ON or OFF 3 Push the MENU button When ON is selected the air conditioner starts stops running when the ON OFF button is pressed and hold 4 seconds When OFF is selected the air conditioner starts stops running when the ON OFF button is pressed Initial setting 2 2 6 Header Follower 7 Language 8 Press hold 4 sec Set Return Press hold 4sec ON OFF Return Fix Set ...

Page 21: ... test operation is released after 60 minutes have passed and returns to the normal operation CAUTION Do not perform the forced test mode for purposes other than the test mode because it applies an excessive load to the devices 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons...

Page 22: ...sted during the test mode Check codes are displayed as usual 3 When the test mode is finished push the button to select 1 Test mode on the Field setting menu screen then push the Set F2 button The screen 3 appears Pushing the Yes F1 button stops the test mode screen and continues the normal operation NOTE The test mode stops after 60 minutes and the screen returns to the normal detailed display 1 ...

Page 23: ...d automatically Automatic loading is not available for some models In this case enter information manually Enter the contact number for service displayed in 2 Service information of 14 information on the menu screen Enter the model name and serial number displayed in 1 Model information of 14 information on the menu screen Push the MONITOR button Refer to 4 Monitor function page 27 for details Whe...

Page 24: ...r model name Enter reset the model name of the indoor unit 5 Indoor unit serial No Enter reset the serial number of the indoor unit 1 Push the button to select 1 Service contact tel No then push the Set F2 button 2 Move the cursor to select the character selected character is highlighted with the F1 F2 button then enter the contact number with the button 3 Push the MENU button 1 Service contact te...

Page 25: ...mation data is loaded automatically from the outdoor unit and displayed Light commercial outdoor unit Enter information manually on the remote controller Service circuit board Enter information manually on the remote controller 1 Push the button to select 2 Outdoor model name on the Register service info screen then push the Set F2 button Select 3 Outdoor unit serial No to enter the serial number ...

Page 26: ... the outdoor unit select 2 Serial No selection of 3 Outdoor unit serial No To select the model name of the indoor unit select 2 Model name selection of 4 Indoor unit model name To select the serial number of the indoor unit select 2 Serial No selection of 5 Indoor unit serial No 2 Push the button to select Remote controller or Outdoor unit When Outdoor unit or Indoor unit is selected the model nam...

Page 27: ...ate and time when the check code occurred for the first time is displayed for the repeated alarm 1 Push the Reset F2 button while the list of Alarm history is displayed 2 Push the Yes F1 button after the confirmation screen is displayed Delete the Alarm history in each remote controller when the dual remote controller system is used 1 Manual model name input 2 Model name selection Outdoor model na...

Page 28: ...4 Monitor function on the Field setting menu screen then push the Set F2 button Push the button to select the code to check data 2 Refer to the Installation Manual supplied with the indoor unit or outdoor unit or service manual for details about the check code and data 3 Push the CANCEL button to return to the Field setting menu screen Monitor function Code 00 Data 0024 Return Set ...

Page 29: ...ition indication for when swinging is cancelled in Fixed position indicator When ON is selected the louver stops and the indication becomes as shown on the right when swinging is cancelled Factory default When OFF is selected the stop position and indication becomes as shown on the right after swinging is cancelled Change the louver operation direction indication in Operation mode When Up Down is ...

Page 30: ...n mode then push the Set F2 button Move with the F1 F2 button to set the setting is displayed for the selected item 2 Push the MENU button to confirm the change and return to the Field setting menu screen Push the CANCEL button to return to the Field setting menu screen without confirming the change Operation mode switching Setting timer operation mode Return Fix ON OFF Set ...

Page 31: ...roup control is used the fan and louver of the selected indoor unit operate Move the cursor to select Code DN with the F1 button then set Code DN with the button Move the cursor to select Data with the F2 button then set Data with the button 2 Refer to the Installation Manual supplied with the indoor unit or service manual for details about the Code DN and Data 3 Push the MENU button to set the ot...

Page 32: ...EH97068301 ...

Reviews: