Refrigerant piping and evacuation

Refrigerant piping

1. Use the following items for the refrigerant 

piping.
Material: Seamless phosphorous deoxidized  
copper pipe.
Wall thickness: 0.03" (0.8 mm) or more 1/2" 

(12.7 mm)
(C1220T-0)
0.04" (1.0 mm) or more for 1-1/8" 
(28.6 mm)
(C1220T-1/2H).

Do not use any copper pipes with a wall  
thickness less than these thicknesses.

2. Flare nut and flare works are also different from 

those of the conventional refrigerant.
Take out the flare nut attached to the main unit of the 
air conditioner, and use it.

REQUIREMENT

When the refrigerant pipe is long, provide support 
brackets at intervals of 8’2” - 9’10” (2.5 - 3 m) to clamp 
the refrigerant pipe. Otherwise, abnormal sound may 
be generated.

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Remove dust and moisture from the inside of the 

connecting pipes.

2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using 

VACUUM PUMP.

4. Check the gas leakage. (Connected points)

Permissible piping length and 
height difference

They vary according to the outdoor unit.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Pipe size

Flaring

• Cut the pipe with a pipe cutter.

Remove burrs completely. 
Remaining burrs may cause gas leakage.

• Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of 
refrigerant R22, the flare tools newly manufactured 
for R410A are recommended.
However, the conventional 
tools can be used by adjusting 
projection margin of the 
copper pipe.

Projection margin in 
flaring : B (Unit : in (mm))

Rigid (Clutch type)

Flaring dia. meter size : A (Unit : in (mm))

* In case of flaring for R410A with the 

conventional flare tool, pull it out approx.

0.02" (0.5 mm) more than that for R22 to 

adjust to the specified flare size.

The copper pipe gauge is useful for 

adjusting projection margin size.

Model 

name

RAV-

SP18 type

SP24, SP30, 

SP36, SP42 

type

Pipe size

Gas side

1/2" 

(12.7 mm)

5/8" 

(15.9 mm)

Liquid side

1/4" 

(6.4 mm)

3/8" 

(9.5 mm)

Outer dia. of copper 

pipe

R410A tool 

used

Conventional 

tool used

R410A

R410A

1/4” (6.4), 3/8” (9.5)

0 - 0.02”

(0 - 0.5)

0.04” - 0.06” 

(1.0 to 1.5)

1/2” (12.7), 5/8” (15.9)

Outer dia. of copper 

pipe

A

+0

–0.02” (-0.4)

R410A

1/4” (6.4)

0.36” (9.1)

3/8” (9.5)

0.52” (13.2)

1/2” (12.7)

0.65” (16.6)

5/8” (15.9)

0.78” (19.7)

B

A

Tightening connection

CAUTION

• Do not apply excessive torque. Otherwise, the nut 

may crack depending on the conditions.

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) 
Therefore, using a torque 
wrench, tighten the flare pipe 
connecting sections which 
connect the indoor and 
outdoor units of the specified 
tightening torque.
Incorrect connections may 
cause not only a gas leak, but 
also a trouble of the 
refrigeration cycle.
Align the centers of the connecting pipes and tighten 
the flare nut as far as possible with your fingers. Then 
tighten the nut with a spanner and torque wrench as 
shown in the figure.

REQUIREMENT

Tightening with an excessive torque may crack the nut 
depending on installation conditions.
Tighten the nut within the specified tightening torque.

Piping with outdoor unit

• Shape of valve differs according to the outdoor unit.

For details of installation, refer to the Installation 
Manual of the outdoor unit.

Evacuation

Using a vacuum pump, perform vacuuming from the 
charge port of valve of the outdoor unit.
For details, follow to the Installation Manual attached to 
the outdoor unit.
• Never use the refrigerant sealed in the outdoor unit 

for air purge.

REQUIREMENT

For the tools such as charge hose, etc., use those 
manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” 
referring to the attached Installation Manual of outdoor 
unit.
Be sure to use a scale to charge the refrigerant of 
specified amount.

REQUIREMENT

• Charging an excessive or too little amount of 

refrigerant causes a trouble of the compressor.
Be sure to charge the refrigerant of specified 
amount.

• A personnel who charged the refrigerant should 

write down the pipe length and the added 
refrigerant amount in the nameplate attached to the 
service panel of the outdoor unit. It is necessary to 
troubleshoot the compressor and refrigeration cycle 
malfunction.

Open the valve fully

Open the valve of the outdoor unit fully. A 4 mm 
hexagonal wrench is required for opening the valve.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas 
leaks or not, from the pipe connecting section or cap of 
the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC 
refrigerant (R410A, R134a, etc.).

Unit : ft•lbs (N•m)

Outer dia. of copper pipe

Tightening torque

1/4" (6.4 mm)

10 - 13 (14 - 18)

3/8" (9.5 mm)

24 - 31 (33 - 42)

1/2" (12.7 mm)

37 - 46 (50 - 62)

5/8" (15.9 mm)

46 - 57 (63 - 77)

Flare at 

indoor 

unit side

Flare at 

outdoor 

unit side

Externally 

threaded side

Half union

Flare nut

Internally 

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

23-EN

24-EN

+00EB99810201_01EN.book  Page 12  Wednesday, June 1, 2016  2:52 PM

Summary of Contents for RAV-SP181BT-UL

Page 1: ...For commercial use Pour usage commercial Indoor Unit Model name Concealed Duct Type RAV SP181BT UL RAV SP241BT UL RAV SP301BT UL RAV SP361BT UL RAV SP421BT UL AIR CONDITIONER SPLIT TYPE Installation Manual 00EB99810201_01EN book Page 1 Wednesday June 1 2016 2 52 PM ...

Page 2: ... different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or ground wires for t...

Page 3: ...e sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connec...

Page 4: ...encies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation ...

Page 5: ...opening size C 29 5 750 41 3 1050 55 1 1400 Space required for attaching or detaching the filter D 28 7 730 23 6 600 40 5 1030 Electrical control box Air filter locally procured 5 9 150 Ceiling opening size 15 5 400 Min 1 Air discharge Ceiling opening size C Electrical control box Check port A 17 7 17 7 450 450 Air discharge 5 9 150 or more Air intake 1 2 30 Ceiling Ceiling Unit width 31 5 800 Cei...

Page 6: ...dle it with plastic band at positions other than specified To install vibration isolation material to hanging bolts confirm that it does not increase the unit vibration External dimensions Unit in mm CORRECT INCORRECT INCORRECT 1 room Hanging bolt 4 M0 4 10 locally procured Hanging bolt pitch B Unit external dimension A Air discharge flange outside C 5 5 140 1 7 44 1 9 49 Outside 8 6 218 2 5 8 147...

Page 7: ...allation of the wired remote control refer to the instructions that are supplied with the control The connection point for the control wiring and the entrance point for the control wiring are clearly marked in the instructions Hanging bolt W3 8 M10 4 pieces Nut W3 8 M10 12 pieces Nut W3 8 M10 M10 flat washer Accessory M10 flat washer Accessory Hanging bolt W3 8 M10 Nut W3 8 M10 Set the air intake ...

Page 8: ...High 0 15 in WG Standard Air Flow 706 cfm 241 type Mid Low 650 700 750 800 850 900 95010001050110011501200 0 45 0 50 0 30 0 35 0 40 0 45 0 15 0 20 0 25 0 30 0 00 0 05 0 10 0 15 Air flow cfm External Static Pressure in WG High 0 46 in WG High 0 35 in WG High 0 25 in WG High 0 15 in WG Mid Low Standard Air Flow 953 cfm 301 type 0 45 0 50 0 30 0 35 0 40 0 15 0 20 0 25 0 00 0 05 0 10 850 900 950100010...

Page 9: ...0 15 in WG Standard Air Flow 706 cfm 241 type Mid Low 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 650 700 750 800 850 900 95010001050110011501200 Air flow cfm External Static Pressure in WG High 0 46 in WG High 0 35 in WG High 0 25 in WG High 0 15 in WG Mid Low Standard Air Flow 953 cfm 301 type 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 850 900 95010001050110011501200125013...

Page 10: ...iece 12 18 1 1 piece 12 25 1 1 piece D H 12 6 320 Remove this cover to install filters in the filter rack Replace the cover after the filters are installed Filter rack W All unit models have the FR 1 FR 2 filter position option available Both positions use the same filters per model shown in the chart above Two positions for filter rack FR 1 FR 2 Indoor unit FR 1 Back air intake flange FR 2 Under ...

Page 11: ...as shown in the following figure Do not provide any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe Connecting drain pipe Insert the drain socket into the connector until the socket can go no farther REQUIREMENT Connect the hard vinyl chloride pipes certainly so that water does not leak by using ad...

Page 12: ...s running Check whether the water is draining from the drain pipe connecting port and check that no water is leaking from the drain pipe After checking that the water drains and there are no water leaks turn off the power connect the float switch connector to its original location CN80 on the printed circuit board and return the electrical control box to its original position When gravity drainage...

Page 13: ...0A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle Align the centers of the connecting pipes and tighten the flare nut as far as possible with your finge...

Page 14: ...se the power cord and control wire of specified thickness type and protective devices required Do not connect 208 230 V power to the terminal blocks U3 U4 A B etc for control wiring Otherwise the system will fail Perform the electric wiring so that it does not come to contact with the high temperature part of the pipe The coating may melt resulting in an accident Do not turn on the circuit breaker...

Page 15: ... Secure the ground wire with the ground screw 4 Fix the wires with a cord clamp Unit in mm CAUTION Firmly tighten the screws of the terminal block Keep the wire length as shown in figure below when it is connected to the terminal block Control wire hole Electrical control box cover Screw Screw Conduit connection hole 3 B S A 4 L L Ground screw Cord clamp Conduit pipe System interconnection wires a...

Page 16: ...erefore install the wired remote control to change the settings Power on SETTING flashes SETTING goes out Remote control is available Approx 5 minutes Power on SETTING flashes SETTING goes out Remote control is available Approx 1 minutes 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the...

Page 17: ...re 4 select the SET DATA of filter sign term from the following table To secure better effect of heating When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room the detection temperature of heating can be raised Also use a circulator or other machinery to circulate heat air near the ceiling Follow to the basic operation procedure 1 ...

Page 18: ...cumulative operating hours x1 h F8 Indoor unit discharge air temperature 1 3 4 2 Group control Group control is not available with the supplied wireless remote control Use the optional wired remote control In case of group control for system of multiple units One remote control can control maximum 8 indoor units as a group In case of group control in single system For wiring procedure and wiring m...

Page 19: ...played Indoor UNIT No before setup change is displayed Procedure 5 1 Using temp setup buttons specify CODE No 14 CODE No 14 Group address 2 Using timer time buttons change the SET DATA from 0001 to 0002 SET DATA Header unit 0001 Follower unit 0002 3 Push button In this time the setup finishes when the display changes from flashing to lighting Procedure 6 If there is other indoor unit to be changed...

Page 20: ... Central control is not available with the supplied wireless remote control Use the optional wired remote control Wiring for central control The terminal block for central control wiring and is the same as that for optional wired remote control Connect the central control wire to the terminals and on the terminal block in the same way as the optional wired remote control For details refer to the I...

Page 21: ...9 or less refrigeration systems when used together with the SMMS series the number of refrigeration systems of the SMMS series is included Since all line addresses are set to 1 except for group control by the automatic address setup function after system power on change the line addresses for each refrigeration system using the wired remote control NOTE For changing setting line addresses using th...

Page 22: ...ter manual system change 9 Test run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L1 to L2 and the grounding If resistance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully To protect the compressor at activa...

Page 23: ...ay disappears operate the air conditioner according to the following Confirmation of trouble history for confirmation Confirmation of trouble history When a trouble occurred on the air conditioner the trouble history can be confirmed with the following procedure The trouble history is stored in memory up to 4 troubles The history can be confirmed from both operating status and stop status Procedur...

Page 24: ...M Outdoor unit P C board Outdoor Outdoor P C board In the case of EEPROM trouble Entire stop H01 Outdoor unit compressor breakdown Outdoor Current detect circuit power voltage Minimum frequency was reached in the current releasing control or short circuit current Idc after direct excitation was detected Wiring trouble of compressor open phase Entire stop H02 Outdoor unit compressor lock Outdoor Co...

Page 25: ...ing etc was detected in the outdoor unit fan drive circuit Entire stop P26 ALT Outdoor unit inverter Idc activated Outdoor IGBT outdoor unit P C board inverter wiring compressor Short circuit protection for compressor drive circuit devices G Tr IGBT was activated Entire stop P29 ALT Outdoor unit position trouble Outdoor Outdoor unit P C board high pressure switch Compressor motor position trouble ...

Page 26: ...EB99810201 00EB99810201_01EN book Page 46 Wednesday June 1 2016 2 52 PM ...

Reviews: