39-EN
40-EN
– 20 –
13
Maintenance
◆
Daily maintenance
Cleaning of air
fi
lter
If is displayed on the remote controller, maintain the
air filter.
1
Push
the
button to stop the
operation, then turn off the circuit breaker.
After the cooling or dry operation, the
ventilation fan keeps running for self-cleaning.
Push the
button twice to stop the
operation.
3
1,2
Take out the air
fi
lter
1
Open the air intake grille until it stops, and
slightly raise the hook on the lower centre
of the air
fi
lter.
The air intake grille should not be opened further;
otherwise, the arms may come off and the air
intake grille may fall down.
Air
fi
lter
Cleaning with water or vacuum cleaner
•
If dirt is heavy, clean the air
fi
lter by tepid water with
neutral detergent or water.
•
After cleaning with water, dry the air
fi
lter suf
fi
ciently
in a shade place.
Mount the air
fi
lter
2
Turn on the circuit breaker, then push the
button on the remote controller to
start the operation.
3
After cleaning, push .
display disappears.
CAUTION
•
Do not start the air conditioner while leaving air
fi
lter removed.
•
Push the
fi
lter reset button. ( indication will be turn off.)
◆
Periodic maintenance
For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner
in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit
at least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner’s expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and
even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Part
Inspection method
Heat exchanger
Access from inspection opening and remove the access panel. Examine the heat exchanger if
there is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Fan
Access from inspection opening and remove the access panel. Examine the fan if there are any
waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the
fi
lter.
Drain pan
Access from inspection opening and remove the access panel. Check if there is any clogging or
drain water is polluted.
▼
Maintenance list
Part
Unit
Check (visual / auditory)
Maintenance
Heat exchanger
Indoor / outdoor
Dust / dirt clogging,
scratches
Wash the heat exchanger when it is clogged.
Fan motor
Indoor / outdoor
Sound
Take appropriate measures when abnormal sound
is generated.
Filter
Indoor
Dust / dirt, breakage
• Wash the
fi
lter with water when it is
contaminated.
• Replace it when it is damaged.
Fan
Indoor
• Vibration, balance
• Dust / dirt, appearance
• Replace the fan when vibration or balance is
terrible.
• Brush or wash the fan when it is contaminated.
Air intake /
discharge grilles
Indoor / outdoor
Dust / dirt, scratches
Fix or replace them when they are deformed or
damaged.
Drain pan
Indoor
Dust / dirt clogging, drain
contamination
Clean the drain pan and check the downward
slope for smooth drainage.
Ornamental panel,
louvres
Indoor
Dust / dirt, scratches
Wash them when they are contaminated or apply
repair coating.
Exterior
Outdoor
• Rust, peeling of insulator
• Peeling / lift of coat
Apply repair coating.
1111056499_(01)_EN.indb 20
1111056499_(01)_EN.indb 20
10/13/14 9:13 AM
10/13/14 9:13 AM