External static pressure
When using the wireless remote controller
To set up the external static pressure, use the DIP switch on the circuit board of the wireless reception part.
For details, refer to the instruction manual of the wireless remote controller kit. Alternatively, use the switch on the
indoor micro computer circuit board as shown in the following figure and table.
* Once switched, the settings “0001”, “0003”, and “0006” can be changed, but to reset to “0000”, you need to set
the switch to the normal (default) position and use a separately-sold wired remote controller to overwrite the data
with “0000”.
SW501
SW501-1
OFF
ON
OFF
ON
SW501-2
OFF
OFF
ON
ON
SET DATA
0000
0001
0003
0006
To reset to the factory default
Switch off SW501-1 and SW501-2, connect a separately-sold
wired remote controller, and then perform the procedure for
installing a separately-sold filter on this page to set the [5d]
data to "0000".
Filter sign setting
To secure better effect of
heating
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [01].
• For the [SET DATA] in Procedure
4
, select the SET
DATA of filter sign term from the following table.
SET DATA
Filter sign term
0000
None
0001
150 H
0002
2500 H
(Factory default)
0003
5000 H
0004
10000 H
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [06].
• For the SET DATA in Procedure
4
, select the SET
DATA of shift value of detection temperature to be
set up from the following table.
Energy saving
Set for the energy saving operation: Energy saving
operation, Set temp. range limit, Return back and
Saving operation.
Refer to the Owner’s Manual supplied with the air
conditioner about “Energy saving operation”, “Saving
operation”.
1
Push the [
˄ ] / [
˅ ] button to select
“Energy saving” on the menu screen, then
push the “
Set” [ F2] button.
2
Push the [
˄ ] / [
˅ ] button to select
the item to set.
3
Push the “
Set” [ F2] button.
Item
Function
1. Energy
saving operation
Perform the power saving
operation of the air conditioner.
2. Set temp.
range limit
Set the temperature range limit of
the remote control operation.
3. Return back
Set the function that changes the
temperature back to the specified
temperature automatically if the
temperature has been changed on
the remote control.
4. Saving operation
Performs operation by
suppressing excessive heating or
excessive cooling through
automatic correction of the
temperature set point.
* “No function” is displayed in
the case of a model for which
the saving operation cannot
be set.
CAUTION
– 21 –
SET DATA
Detection temperature shift value
0000
No shift
0001
+1.8 °F (+1 °C)
0002
+3.6 °F (+2 °C)
(Factory default)
0003
+5.4 °F (+3 °C)
0004
+7.2 °F (+4 °C)
0005
+9.0 °F (+5 °C)
0006
+10.8 °F (+6 °C)