– 34 –
Heat insulating process
• As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom
of the indoor unit tightly.
• Cover the drain pipe tightly with a heat insulator procured locally so that it overlaps with the attached heat
insulator of the drain connecting section.
Connecting method of the duct
CAUTION
Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop.
Wrap the attached heat insulator tightly from
the surface of the indoor unit.
Heat insulator of the drain
connecting section
(accessory)
In
do
or
u
n
it
Heat insulator
(locally procured)
Flange (locally procured)
Aluminum tape (locally procured)
Aluminum tape (locally procured)
Under surface
Air discharge side
Indoor unit
Air intake side
Connect a duct to the
outside of the flange
Duct: Insulation materia
(locally procured)
Flange
Fan characteristics
SM40
SM45
SM56
SM80
SM110
SM140
SM160
0
20
40
60
80
100
120
140
160
380
480
580
680
780
880
980
Standard air volume: 800 m
3
/h
Upper limit of
external static
pressure (120 Pa)
High
(120 Pa)
Lower limit of external
static pressure (120 Pa)
Low
(120 Pa)
Standard filter pressure loss
E
x
te
rn
al
sta
tic
pr
e
ssu
re
(
P
a)
Air Volume (m
3
/h)
High
(100 Pa)
High
(80 Pa)
High
(65 Pa)
High
(50 Pa)
High
(40 Pa)
High
(30 Pa)
0
20
40
60
80
100
120
140
160
570
770
670
970
870
1170
1070
1370
1270
1470
Standard air volume: 1200 m
3
/h
Upper limit of
external static
pressure (120 Pa)
High
(120 Pa)
Lower limit of external
static pressure (120 Pa)
Low
(120 Pa)
Standard filter pressure loss
E
x
te
rn
al
sta
tic
pr
e
ssu
re
(
P
a)
Air Volume (m
3
/h)
High
(100 Pa)
High
(80 Pa)
High
(65 Pa)
High
(50 Pa)
High
(40 Pa)
High
(30 Pa)
0
20
40
60
80
100
120
140
160
1000
1200
1400
1600
1800
2000
2200
2400
2600
Standard air volume: 2100 m
3
/h
Upper limit of
external static
pressure (120 Pa)
High
(120 Pa)
Lower limit of external
static pressure (120 Pa)
Low
(120 Pa)
Standard filter pressure loss
E
x
te
rn
al
sta
tic
pr
e
ssu
re
(
P
a)
Air Volume (m
3
/h)
High
(100 Pa)
High
(80 Pa)
High
(65 Pa)
High
(50 Pa)
High
(40 Pa)
High
(30 Pa)
67-EN
68-EN