Applicable controls
• For using the wired remote controller RBC-AMS55E*,
refer to the Owner’s Manual attached to the wired
remote controller.
REQUIREMENT
• When you use this air conditioner for the first time, it takes
approx. 5 minutes until the remote controller becomes
available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes
approx. 5 minutes
until the remote controller
becomes available.
<When power is turned on for the second (or later)
time>
It takes
approx. 1 minute
until the remote controller
becomes available.
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the settings.
Basic procedure for changing
settings
Change the settings while the air conditioner is not working.
(Be sure to stop the air conditioner before making settings.)
1
Push
button and temp. setup
button
simultaneously for at least 4 seconds or more.
After a while, the display flashes as shown in the figure.
Confirm that the CODE No. is [01].
• If the CODE No. is not [01], push
button to erase
the display content, and repeat the procedure from
the beginning.
(No operation of the remote controller is accepted for
a while after
button is pushed.)
2
Each time you push
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs. You can confirm
the indoor unit for which you want to change
settings.
3
Using temp. setup
/
buttons, specify
CODE No. [
].
4
Using timer time
/
buttons, select
SET DATA [
].
* The settings cannot be changed using the wireless
remote controller, sub remote controller, or remote-
controllerless system (for central remote controller
only). Therefore, install the wired remote controller to
change the settings.
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller
is available
Approx. 5 minutes
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller
is available
Approx. 1 minutes
1
6
1
3
2
5
4
(* Display content varies with
the indoor unit model.)
5
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat from
2
.
• To change other settings of the selected indoor unit,
repeat from
3
.
Use
button to clear the settings.
To make settings after
button was pushed, repeat
from
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote controller is accepted.)
External static pressure
settings
Be sure to set up a tap change based upon the resistance
(external static pressure) of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
2
3
4
5
6
).
• Specify
[5d]
to the CODE No. in
3
.
• For the setup data of
4
, select a setup data of the external
static pressure to be set up from the following table.
<Change on wired remote controller>
The list above is when SW501-1 and SW501-2 is OFF.
* Except standard filter pressure loss.
◆
When wireless remote controller
is used
The settings can be changed with the switch on the indoor
P.C. board.
* Except standard filter pressure loss.
** When setting the external static pressure to 10 Pa, set
SW501-1 and SW501-2 to OFF, connect a separately sold
wired remote controller, and then set the data of CODE No.
[5d] to “0000” in “External static pressure settings” on this
page.
◆
To restore the factory default
To return the DIP switch settings to the factory defaults, set
SW501-1 and SW501-2 to OFF, connect a separately sold
wired remote controller, and then set the data of CODE No.
[5d] to “
0003
” in “External static pressure settings” on this
page.
Setup data [5d]
External static pressure
0000
10 Pa*
0001
20 Pa*
0003
30 Pa* (Factory default)
0006
50 Pa*
SW501-1
SW501-2
Setup data
External static
pressure
OFF
OFF
0003
30 Pa*
(Factory default)
OFF
OFF
0000**
10 Pa*
ON
OFF
0001
20 Pa*
OFF
ON
0003
30 Pa*
ON
ON
0006
50 Pa*
SW501-1
MCU(IC501)
SW501-2
115-EN
116-EN