– 3 –
1. SPECIFICATIONS
RAV-M242A-E / RAV-M242A
2 indoor unit
A
B
12, 200 x 2
6, 100
24, 400
7,1
1
220 – 240
50
2,46
99
10,8
68
53
R-22
0,95 + 0,95
Capillary tube
ø12,7 (1/2")
Flare
ø6,4 (1/4")
Flare
7,6 (25)
15 (48)
2 ( 7 )
5 (16)
5 (16)
RAS-13SK-E or RAS-13SKX
RAV-M242A-E or RAV-M242A
790 (2 – 7 1/8)
880 (2 – 9 1/8)
310 (1 – 1/4)
70 (154,3)
Finned tube
Propeller fan
63
PH160X2-4L
1,100
Fuse, inner overload-relay
Model
Item
Operation
Unit
*1 BTU/h
kcal/h
Cooling capacity
*1 BTU/h
kW
Phase
Power source
V
Hz
Power consumption
Cooling
kW
Power factor
Cooling
%
Running current
Cooling
A
Starting current
Cooling
A
Operating noise (SPL*4)
dB (A)
Refrigerant
Name of refrigerant
Charge volume
kg
Refrigerant control
Gas side size
mm (in.)
Coupler style
Liquid side size
mm (in.)
Coupler style
Standard length
m (ft)
Maximum length (One-way) *2
m (ft)
Minimum length
m (ft)
Maximum height
Indoor unit higher
m (ft)
Outdoor unit higher
m (ft)
INDOOR UNIT MODEL
OUTDOOR UNIT MODEL
Height
mm (ft-in.)
Dimensions
Width
mm (ft-in.)
Depth
mm (ft-in.)
Net weight
kg (Ibs)
Condenser type
Condenser fan type
Fan motor output
W
Compressor
Model
Output
W
Protective device
Condenser air inlet temperature
35°C DB (95°F DB)
Evaporator air inlet temperature
27°C DB (80°F DB)
19,0°C WB (66°F WB)
Note 1: Cooling capacity is based on the following temperature conditions.
Note 2: These mean equivalent length.
Note 3: Operating range of the units
Note 4: SPL: Sound Pressure Level
Note 5: Specifications are subject to change without notice.
Remark:
• Be sure to refer to the service manual file No. A00-9701 for the indoor unit RAS-13SKX (or RAS-13SK-E) to be
connected.
Condenser air inlet temperature
43°C DB (109°F DB)
21°C DB (70°F DB)
Evaporator air inlet temperature
32°C DB, 22,5°C WB
(95°F DB, 73°F WB)
21°C DB, 15,5°C WB
(70°F DB, 60°F WB)
Maximum
Minimum
Summary of Contents for RAV-M242A
Page 23: ... 23 7 5 P C Board Layout Top View Bottom View ...
Page 28: ......