background image

28-EN

27-EN

– 14 –

EN

7

Electrical connection

 WARNING

• 

Use the speci

fi

ed wires for wiring connect the terminals. Securely 

fi

x them to prevent external forces 

applied to the terminals from affecting the terminals.

Incomplete connection or 

fi

xation may cause a 

fi

re or other trouble.

• 

Connect earth wire. (grounding work)

Incomplete earthing cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.

• 

Appliance shall be installed in accordance with national wiring regulations.

Capacity shortage of power circuit or incomplete installation may cause an electric shock or a 

fi

re.

• 

Under no circumstances, the power supply wire or the indoor and outdoor connecting wire must not 
be connected in the middle (Connection using a solderless terminal etc.)

Connection trouble in the places where the wire is connected in the middle may give rise to smoking and/or a 

fi

re.

 CAUTION

•  For power supply speci

fi

cations, follow the Installation Manual of outdoor unit.

•  Do not connect 220 – 240V power to the terminal blocks ( 

A

 , 

B

 ) for control wiring.

Otherwise, the system will fail.

•  Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires 

during peeling them.

•  Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.

The coating may melt resulting in an accident.

•  Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.

 

„

Wiring speci

fi

 cations

Indoor / Outdoor connecting wires speci

fi

cations

Indoor unit power supplied from outdoor unit

•  The outdoor unit power supply patterns vary on models.

Indoor unit power supply

1~50 Hz
1~60 Hz

220 - 240V
220V

Indoor / Outdoor connecting wires*

4 × 1.5 mm² or more (H07 RN-F or 60245 IEC 66)*

Up to 70 m

*Number of wire x wire size
*Including earth line

Remote controller wiring

Remote controller wiring, remote controller inter-unit wiring

Wire size: 2 × 0.5 to 2.0 mm

2

Total wire length of remote controller wiring and remote 
controller inter-unit wiring = L + L1 + L2 + … Ln

In case of wired type only

Up to 500 m

2 remote controllers

Up to 300 m

In case of wireless type included

Up to 400 m

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 200 m

*  The remote controller wiring length differs depending on the remote controller used. For details, refer to the 

Installation Manual attached to the remote controller.

 CAUTION

The remote controller wire and Indoor / Outdoor connecting wires cannot be parallel to contact each other and 
cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise 
or other factor.

 

„

Communication type

TU2C-Link can be used with these models.
If the indoor unit and the connected remote controller / remote sensor are all TU2C-Link models, TU2C-Link 
communication will be performed automatically.
(If the TCC-Link model is included, TCC-Link communication will be performed.)
For details of communication type, refer to the following table.

Communication type and model names

Communication 

type

TU2C-Link

TCC-Link

Indoor unit

RAV-HM

½½½

 series model

Other than RAV-HM

½½½

 series

Wired remote 
controller

RBC-A

½½

U

½½½

This letter indicates U series model.

Other than U series

Wireless remote 
controller kit & 
receiver unit

RBC-AXU

½½½

This letter indicates U series model.

Other than U series

Remote sensor

TCB-TC

½½

U

½½½

This letter indicates U series model.

Other than U series

 CAUTION

When connecting to the central control device dedicated to TCC-Link, it is necessary to change to TCC-Link 
using a wired remote controller. Set according to the Communication type procedure of “8 Applicable controls”.

 

 

 

L1

L

L2

Ln

Remote 

controller 

wiring

Remote controller inter-unit wiring

For number of Max. connectable units, 

refer to the following table.

Indoor unit

Remote 

controller

Indoor unit

Indoor unit

Indoor unit

Max. number of connect-able indoor units, and communication type

Unit type

Indoor unit

RAV-HM

½½½

RAV-HM

½½½

½

½

Remote controller
Remote sensor

U series

½

U series

½

Communication type

TU2C-Link

TCC-Link

Max. number of connect-able 
units

16

8

½

 : Other than RAV-HM

½½½

 and U series

Summary of Contents for RAV-HM301U1TP-E

Page 1: ...AIR CONDITIONER SPLIT TYPE Installation Manual Indoor Unit Model name 1 Way Cassette type RAV HM301U1TP E RAV HM401U1TP E English For commercial use ...

Page 2: ...T This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer Be sure to check the refrigerant type for outdoor unit to be combined and then install it Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 8 4 Insta...

Page 3: ...o electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation repair relocati...

Page 4: ... work required Before carrying out the installation maintenance repair or removal work set the circuit breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Warning indica...

Page 5: ...ditioner must be transported by hand carry it by two or more people Do not move or repair any unit by yourself There is high voltage inside the unit You may get electric shock when removing the cover and main unit This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Selection of installation location When the air condition...

Page 6: ...at it is not slack Electrical wiring Only a qualified installer 1 or qualified service person 1 is allowed to carry out the electrical work of the air conditioner Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks To connect the electrical wires repair the electrical parts or ...

Page 7: ...tion work check for refrigerant leaks and check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly Explanations given to user Upon completion of the installation work tell the user where the circuit breaker is located If the user does not know where the circuit breaker is he or she will not be able to turn it off in the even...

Page 8: ... in this Installation Manual please refer to the enclosed CD R Owner s Manual 1 Hand over to customers For other languages that do not appear in this Installation Manual please refer to the enclosed CD R CD ROM 1 Owner s Manual and Installation Manual Heat insulating pipe 2 For heat insulation of pipe connecting section Installation pattern 1 For confirmation of ceiling opening and indoor unit pos...

Page 9: ...ghbour pay due attention to the level of noise y Place with poor ventilation Before air ducting work check whether value of air volume static pressure and duct resistance are correct y Do not use the air conditioner for special purposes such as preserving food precision instruments or art objects or where breeding animals or growing plants are kept This may degrade the quality of preserved materia...

Page 10: ... a ceiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their connection locations before hanging the indoor unit Procure hanging bolts and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Using the installation pattern accessory The installation patt...

Page 11: ... y Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage y Remove the adjust corner caps at the four corners of the ceiling panel and then install the ceiling panel onto the indoor unit y Make sure that the claws of the four adjust corner caps are securely fit I...

Page 12: ...se to the clear drain socket If applying the adhesive socket will be damaged and cause water leakage 5 mm or less 10 to 12 mm hose band tightening margin VP25 vinyl chloride pipe Locally procured 10 mm Socket for VP25 vinyl chloride pipe Locally procured Flexible hose Accessory Heat insulator Drain pipe connecting port Transparent Indoor unit Connecting drain pipe y Connect a hard socket locally p...

Page 13: ...ails refer to the Installation Manual attached to the outdoor unit CAUTION IMPORTANT 4 POINTS FOR PIPING WORK 1 Reusable mechanical connectors and flared joints are not allowed indoors When mechanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be refabricated 2 Tight connection between pipes and unit 3 Evacuate the air in...

Page 14: ...al of outdoor unit Use a scale to charge the refrigerant of specified amount REQUIREMENT y Charging an excessive or too little amount of refrigerant causes a trouble of the compressor Charge the refrigerant of specified amount y A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the F GAS label of the outdoor unit It is necessary to fix th...

Page 15: ...0 mm2 Total wire length of remote controller wiring and remote controller inter unit wiring L L1 L2 Ln In case of wired type only Up to 500 m 2 remote controllers Up to 300 m In case of wireless type included Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200 m The remote controller wiring length differs depending on the remote controller used For details refer...

Page 16: ...ttached on left side Wire type Specification Cable clamping position Cabtyre cable 4 core stranded wire 2 5 mm Side D Cabtyre cable 4 core stranded wire 1 5 mm Side C Side D Space 8 5 mm Side C Space 4 mm Power supply terminal block Cord clamp Remote controller terminal block Hinge Screw Louver connector CN510 White Earth wire Power supply wire Wiring between indoor unit and outdoor unit 1 Figure ...

Page 17: ... 1 minute until the remote controller becomes available Approx 5 minutes Power on SETTING flashes SETTING goes out Remote controller is available Normal settings were made when the indoor unit was shipped from factory Change the indoor unit settings as required Use the wired remote controller to change the settings The settings cannot be changed using the wireless remote controller sub remote cont...

Page 18: ...nit senses room temperature usually Set the remote controller sensor to sense the temperature around the remote controller Select items following the basic operation procedure 1 2 3 4 5 6 7 y Specify 32 for the Code No in Procedur 4 y Select the following data for the Set data in Procedure 5 Set data Remote controller sensor 0000 Not in use Factory default 0001 In use When flashes the remote contr...

Page 19: ...necessary to change the address manually after setup of the automatic address according to the system configuration of the group control The follow mentioned system configuration is a case when complex systems in which systems of the simultaneous twin unit is controlled as a group by a remote controller Example Group control for complex system Outdoor unit Outdoor unit Procedure example 1 Indoor u...

Page 20: ...ith the wired remote controller as usual For the procedure of the operation refer to the attached Owner s Manual A forced test run can be executed in the following procedure even if the operation stops by thermostat OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION Do not use the forced test run for ca...

Page 21: ...troller T Cooling test run ON OFF 17 C 18 C 17 C 18 C 17 C 18 C 17 C test run ON OFF T Heating test run ON OFF 30 C 29 C 30 C 29 C 30 C 29 C 30 C test run ON OFF Monitoring function This function can be used to call the service monitor mode from the remote controller during a test run to obtain the temperature of the sensors of the remote controller indoor unit and outdoor unit 2 4 3 5 1 1 2 4 Mon...

Page 22: ...out the detergent y After rinsing the panel and air filter with water dry it in the shade 1 Close the air inlet grille y Close the air inlet grille slide the hook inward and fix the air inlet grille securely Hook lock grille Hook lock grille Air inlet grille Loosen screw Direction to close Direction to close Push grille 2 Turn on the circuit breaker then push the button on the remote controller to...

Page 23: ...e y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ornamental panel louvers Ind...

Page 24: ...unit discharge temp trouble Outdoor An trouble was detected in the discharge temp releasing control Entire stop Check codes and parts to be checked Wired remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked trouble description Air conditioner status Indication Operation Timer Ready GR GR OR Flashing E01 ...

Page 25: ...ire stop P19 ALT 4 way valve trouble Outdoor Indoor 4 way valve indoor temp sensors TC TCJ An trouble was detected due to temperature drop of the indoor unit heat exchanger sensor when heating Auto reset P20 ALT High pressure protective operation Outdoor High pressure protection Entire stop P22 ALT Outdoor unit fan trouble Outdoor Outdoor unit fan motor outdoor unit P C board An trouble overcurren...

Page 26: ... becomes invalid if technical or operational modifications are introduced without the manufacturer s consent Declaration of Conformity Manufacturer Toshiba Carrier Thailand Co Ltd 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery des...

Page 27: ...e risk of suffocation if its concentration should rise excessively Suffocation from leakage of R32 is almost non existent With the recent increase in the number of high concentration buildings however the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space individual control energy conservation by curtailing heat and carrying power ...

Page 28: ... No 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 1 0002 HIGH CEILING 3 0003 High ceiling setup CODE No 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time Code N...

Page 29: ...uantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester ...

Page 30: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1131350101 ...

Reviews: