background image

30-EN

29-EN

– 15 –

 

„

How to open the valve

Fully open the valves of the outdoor unit. (First fully 
open the valve on the liquid side, and then fully open 
the valve on the gas side.)
*  Do not open or close the valves when the ambient 

temperature is -20°C or less. Doing so may damage 
the valve O-rings and result in refrigerant leakage.

Liquid side, gas side

Open the valve with hexagon wrench.
[Hexagonal wrench is required.]

Hexagonal wrench size

Liquid side

Gas side

GM56

4 mm

4 mm

GM80

4 mm

5 mm

Valve handling precautions

 

y

Open the valve stem until it strikes the stopper.

  It is unnecessary to apply further force.

 

y

Securely tighten the cap with a torque wrench.

Cap tightening torque

Valve size

Ø6.4 mm

14 to 18 N•m
(1.4 to 1.8 kgf•m)

Ø9.5 mm

14 to 18 N•m
(1.4 to 1.8 kgf•m)

Ø12.7 mm

33 to 42 N•m
(3.3 to 4.2 kgf•m)

Ø15.9 mm

33 to 42 N•m
(3.3 to 4.2 kgf•m)

Charge port

14 to 18 N•m
(1.4 to 1.8 kgf•m)

 

„

Replenishing refrigerant

This model is a 20 m chargeless type that does not 
need to have its refrigerant replenished for refrigerant 
pipes up to 20 m. When a refrigerant pipe longer than 
20 m is used, add the speci

fi

ed amount of refrigerant.

Refrigerant replenishing procedure

1. After vacuuming the refrigerant pipe, close the 

valves and then charge the refrigerant while the air 
conditioner is not working.

2. When the refrigerant cannot be charged to the 

speci

fi

ed amount, charge the required amount of 

refrigerant from the charge port of the valve on the 
gas side during cooling.

Requirement for replenishing refrigerant

Replenish liquid refrigerant.
When gaseous refrigerant is replenished, the 
refrigerant composition varies, which disables normal 
operation.

 

„

Air purge

With respect to the preservation of the terrestrial 
environment, adopt “Vacuum pump” to purge air 
(Evacuate air in the connecting pipes) when installing 
the unit.

 

y

Do not discharge the refrigerant gas to the 
atmosphere to preserve the terrestrial environment.

 

y

Use a vacuum pump to discharge the air (nitrogen, 
etc.) that remains in the set. If air remains, the 
capacity may decrease.

For the vacuum pump, be sure to use one with a 
back

fl

ow preventer so that the oil in the pump does not 

back

fl

ow into the pipe of the air conditioner when the 

pump stops.
(If oil in the vacuum pump is put in an air conditioner 
including R32/R410A, it may cause trouble with the 
refrigeration cycle.)

Compound pressure gauge

Pressure gauge

Gauge manifold 

valve

Handle High 

(Keep fully closed)

Charge hose 

(For R32/R410A)

Vacuum pump adapter 

for counter

fl

ow 

prevention 

(For R32/R410A)

Vacuum 

pump

Charge port 

(Valve core 

(Setting pin))

Charge hose 

(For R32/R410A)

Handle Low

–101 kPa 

(–76 cmHg)

Packed valve at gas side

Vacuum pump

As shown in the 

fi

gure, connect the charge hose after 

the manifold valve is closed completely.

Attach the connecting port of the charge hose with a 

projection to push the valve core (setting pin) to the 

charge port of the set.

Open Handle Low fully.

Turn ON the vacuum pump. (*1)

Loosen the 

fl

are nut of the packed valve (Gas side) 

a little to check that the air passes through. (*2)

Retighten the 

fl

are nut.

Execute vacuuming until the compound pressure gauge 

indicates –101 kPa (–76 cmHg). (*1)

Close Handle Low completely.

Turn OFF the vacuum pump.

Leave the vacuum pump as it is for 1 or 2 minutes, and 

check that the indicator of the compound pressure gauge 

does not return.

Open the valve stem or valve handle fully.

(First, at liquid side, then gas side)

Disconnect the charge hose from the charge port.

Tighten the valve and caps of the charge port securely.

*1:  Use the vacuum pump, vacuum pump adapter, and gauge 

manifold correctly referring to the manuals supplied with 

each tool before using them.

    Check that the vacuum pump oil is 

fi

lled up to the speci

fi

ed 

line of the oil gauge.

*2:  When air is not charged, check again whether the 

connecting port of the discharge hose, which has a 

projection to push the valve core, is 

fi

rmly connected to the 

charge port.

Summary of Contents for RAV-GM561ATJP-E

Page 1: ...AIR CONDITIONER SPLIT TYPE Installation Manual Outdoor Unit Model name RAV GM561ATP E RAV GM561ATJP E RAV GM801ATP E RAV GM801ATJP E For commercial use English ...

Page 2: ...run 18 11 Annual maintenance 18 12 Air conditioner operating conditions 18 13 Functions to be implemented locally 18 14 Troubleshooting 21 15 Appendix 21 16 Specifications 23 Original instruction ADOPTION OF R32 REFRIGERANT This air conditioner adopts the HFC refrigerant R32 which does not destroy the ozone layer This outdoor unit is designed exclusively for use with R32 refrigerant Be sure to use...

Page 3: ...and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he...

Page 4: ...ng the contents below meanings of indications and be sure to follow the description Indication Meaning of Indication WARNING Text set off in this manner indicates that failure to adhere to the directions in the warning could result in serious bodily harm 1 or loss of life if the product is handled improperly CAUTION Text set off in this manner indicates that failure to adhere to the directions in ...

Page 5: ... in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Only a qualified installer 1 or qualified service person 1 is allowed to undertake work at heights using a stand of 50 cm or more Wear protective gloves and safety work clothing during installat...

Page 6: ...nes Pipe work shall be protected from physical damage Compliance with national gas regulations shall be observed Selection of installation location If you install the unit in a small room take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks Consult the dealer from whom you purchased the air conditioner when you implement the measures Accumula...

Page 7: ...nd relocation work follow the instructions in the Installation Manual and use tools and pipe components specifically made for use with R32 refrigerant If pipe components not designed for R32 refrigerant are used and the unit is not installed correctly the pipes may burst and cause damage or injuries In addition water leakage electric shock or fire may result Nitrogen gas must be used for the airti...

Page 8: ...ster such as a leak or electric shock is caused at user s side Upon completion of the installation work check for refrigerant leaks and check the insulation resistance and water drainage Then conduct a test run to check that the air conditioner is operating properly After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a fire s...

Page 9: ...ccumulation of highly concentrated refrigerant may cause a fire hazard Therefore be sure to follow the installation space instructions in the Installation Manual and provide open space on at least one of the four outdoor unit sides In particular when both the discharge and intake sides face walls and obstacles are also placed on both sides of the outdoor unit take steps to provide space wide enoug...

Page 10: ...rant units For connecting pipes use new and clean piping materials with high pressure fittings made for the R32 or R410A only so that water and or dust does not enter y When using existing piping refer to 15 APPENDIX 1 Existing piping Required Tools Equipment and Precautions for use Prepare the tools and equipment listed in the following table before starting the installation work Newly prepared t...

Page 11: ...n company y Proper earthing can prevent charging of electricity on the outdoor unit surface due to the presence of a high frequency in the frequency converter inverter of the outdoor unit as well as prevent electric shock If the outdoor unit is not properly earthed you may be exposed to an electric shock y Be sure to connect the earth wire grounding work Incomplete grounding can cause an electric ...

Page 12: ... durable enough to support the weight of the outdoor unit Insufficient durability may cause the outdoor unit to fall which may result in injury Pay special attention when installing the unit onto a wall surface CAUTION Do not install the outdoor unit in a location that is subject to combustible gas leaks Accumulation of combustible gas around the outdoor unit may cause a fire Install the outdoor u...

Page 13: ... leg that is in contact with and underneath the bottom plate of the outdoor unit When installing the foundation for an outdoor unit with downward piping consider the piping work Absorb vibration with vibration proof rubber pads Fixing leg Foundation Correct Bottom plate of outdoor unit Foundation Correct Support the bottom surface of the fixing leg that is in contact with and underneath the bottom...

Page 14: ...he specified tightening torque Incomplete connections may cause not only a gas leak but also trouble with the refrigeration cycle Do not apply refrigerating machine oil to the flared surface 5 Refrigerant piping Optional installation parts Locally procured Parts name Q ty A Refrigerant piping Liquid side Ø6 4 9 5 mm Gas side Ø12 7 15 9 mm One each B Pipe insulating material polyethylene foam 6 mm ...

Page 15: ...cing valve Nitrogen gas CAUTION Never use oxygen flammable gas or noxious gas for the airtight test Gas leak check Step 1 Pressurize to 0 5 MPa 5 kg cm G for 5 minutes or longer Major leaks can be discovered Step 2 Pressurize to 1 5 MPa 15 kg cm G for 5 minutes or longer Step 3 Pressurize to 4 15 MPa 42 kg cm G for 24 hours Micro leaks can be discovered However note that when the ambient temperatu...

Page 16: ...rigerant gas to the atmosphere to preserve the terrestrial environment y Use a vacuum pump to discharge the air nitrogen etc that remains in the set If air remains the capacity may decrease For the vacuum pump be sure to use one with a backflow preventer so that the oil in the pump does not backflow into the pipe of the air conditioner when the pump stops If oil in the vacuum pump is put in an air...

Page 17: ...ion Leak detectors for conventional HCFC refrigerant R22 etc cannot be used as the sensitivity drops to approximately 1 40 when used for HFC refrigerant y R32 has a high working pressure so failure to perform the installation work properly may result in gas leaks such as when the pressure rises during operation Be sure to perform leak tests on the piping connections Insulating the Pipes y The temp...

Page 18: ...t Incorrect connection may cause a failure For the air conditioner connect a power wire with the following specifications Model RAV GM56 GM80 Power supply 220 240 V 50 Hz 220 V 60 Hz Maximum running current 15 5 A Installation fuse rating 20 A all types can be used Power supply wire H07 RN F or 60245 IEC 66 2 5 mm or more System interconnection wires H07 RN F or 60245 IEC 66 1 5 mm or more How to ...

Page 19: ...r units are strongly recommended As a general rule if an indoor unit is operated for about 8 hours daily the indoor outdoor units will need to be cleaned at least once every 3 months This cleaning and maintenance should be carried out by a qualified service person Failure to clean the indoor outdoor units regularly will result in poor performance icing water leaking and even compressor failure 12A...

Page 20: ...en to recover the refrigerant 1 Operate the indoor unit in the fan mode 2 Check that the LED displays are placed in their initial status If not place them in the initial status 3 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 1 4 Press SW01 once to set the LED displays D800 to D805 to the refrigerant recovery LED display shown below Fig 2 Fig 1 Fig 2 LED displays indi...

Page 21: ...r at least 5 seconds to return to the initial status and then repeat the setting steps How to check the existing piping settings You can check whether the existing piping settings are enabled 1 Check that the LED displays are placed in their initial status If not place them in the initial status 2 Hold down SW01 for at least 5 seconds and check that D804 flashes slowly Fig 9 3 Press SW01 four time...

Page 22: ...re to use new pipes for the refrigerant piping works y The operating pressure of R32 is high If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thickness mm Pipe outer diameter Ø6 4 Ø9 5 Ø12 7 Ø15 9 Ø19 0 Thickness R32 R410A 0 8 0 8 0 8 1 0 1 0 R22 y In case the pipe diame...

Page 23: ...be used y Use new pipes Clean the pipes or use new pipes Piping necessary to change the flare nut machining size due to pipe compression 1 Flare nut width H H mm Copper pipe outer diameter Ø6 4 Ø9 5 Ø12 7 Ø15 9 Ø19 0 For R32 R410A 17 22 26 29 36 For R22 Same as above 24 27 Same as above 2 Flare machining size A A mm Copper pipe outer diameter Ø6 4 Ø9 5 Ø12 7 Ø15 9 Ø19 0 For R32 R410A 9 1 13 2 16 6...

Page 24: ...Weight kg Cooling Heating RAV GM561ATP E 40 RAV GM561ATJP E 40 RAV GM801ATP E 42 RAV GM801ATJP E 42 Under 70 dBA Amin m 30 25 20 15 10 5 0 0 8 0 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 M kg Ceiling mounted unit Wall mounted unit F l o o r s t a n d i n g u n i t ...

Page 25: ...r charging or recovering location and where possible adjacent to existing nameplates or product information label 2 Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink Then place the included transparent protective sheet over the label to prevent the writing from rubbing off 3 Prevent emission of the contained fluorinated greenhouse gas Ensure that the fluor...

Page 26: ...rise excessively Suffocation from leakage of R32 is almost non existent If a conditioner system is to be installed in a small room select a suitable model and installation procedure so that if the refrigerant accidentally leaks out its concentration does not reach the limit and in the event of an emergency measures can be made before injury can occur In a room where the concentration may exceed th...

Page 27: ...1124151101 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Reviews: