– 16 –

EN

ID

ID

The appliance shall be installed in 
accordance with national wiring regulations.

Capacity shortages of the power circuit or an
incomplete installation may cause an electric
shock of fire.

Be sure to connect the earth wire. 
(grounding work)
Incomplete grounding may lead to electric
shock.

Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
wires.

Using the specified wires, ensure that the
wires are connected, and fix wires securely 
so that the external tension to the wires 
does not affect the connecting part of the 
terminals.

Incomplete connection or fixation may cause a
fire, etc.

‡ 5HPRYHWKHSDQHODQG\RXFDQVHHHOHFWULFSDUWV

  on the front side.

‡ $PHWDOSLSHFDQEHLQVWDOOHGWKURXJKWKHKROHIRU

  wiring. If the hole size does not fit the wiring pipe to

 EHXVHGGULOOWKHKROHDJDLQWRDQDSSURSULDWHVL]H
‡

Be sure to clamp the power wires and indoor/outdoor

 FRQQHFWLQJZLUHVZLWKDEDQGLQJEDQGDORQJWKH

  connecting pipe so that the wires do not touch the
  compressor or discharge pipe.

 7KHFRPSUHVVRUDQGWKHGLVFKDUJHSLSHEHFRPH

 hot.)

)XUWKHUPRUHEHVXUHWRVHFXUHWKHVHZLUHVZLWKWKH
SLSHYDOYHIL[LQJSODWHDQGFRUGFODPSVVWRUHGLQWKH
HOHFWULFSDUWVER[

‡

Connect the indoor/outdoor connecting wires to the

 LGHQWLFDOWHUPLQDOQXPEHURQWKHWHUPLQDOEORFNRI

 each 

unit.

  Incorrect connection may cause a failure.

WARNING

1

2

3

Wiring between Indoor Unit
and Outdoor Unit 

The dashed lines show on-site wiring

Circuit 

EUHDNHU

Outdoor unit

Indoor unit

Wired 
remote 
controller

Input power 

380–415V 3N~, 50Hz
380V 3N~, 60Hz

7

Electrical work

CAUTION

‡ $

n installation fuse must 

E

e used for the power supply 

line of this air conditioner.

‡

Incorrect / incomplete wiring may lead to an electrical 
fire or smoke.

‡

Prepare an exclu

VLY

e power supply for the air 

conditioner.

‡

This product can 

E

e connected to the mains power.

 

Fixed wire connections:

 

$VZLWF

h that disconnects all poles and has a contact 

separation of at least 3 mm must 

E

e incorporated in 

the fixed wiring.

‡

Be sure to use the cord clamps attached to the 
product.

‡

Do not damage or scratch the conducti

Y

e core or inner 

insulator of the power and system interconnection 
wires when peeling them.

‡

Use the power and system interconnection wires with 
specified thicknesses, specified types and prote

FWLY

de

YLFHV

 required.

Electric parts 

ER[

Cord 
clamp

Pipe 
hole

6HUYLFH

panel

Gas leak inspection

Use a leak detector manufactured specially for HFC refrigerant
(R32, R410A, R134a, etc.) to perform the R32 gas leak inspection.

*  Leak detectors for conventional HCFC refrigerant (R22, etc.) 

cannot be used, as the sensitivity drops to approximately 1/40 
when used for HFC refrigerant.

• 

R32 has a high working pressure, so failure to perform the installation 
work properly may result in gas leaks such as when the pressure 
rises during operation. Be sure to perform leak tests on the piping 
connections.

Indoor unit inspection locations

(piping connections)

Refrigerant
piping

Indoor unit side piping

Outdoor unit inspection locations

 

Insulating the Pipes

• 

The temperatures at both the liquid side and gas 
side will be low during cooling so in order to prevent 
condensation, be sure to insulate the pipes at both 
of these sides.

• 

Insulate the pipes separately for the liquid side and 
gas side.

• 

Insulate the branch pipes by following the 
instructions in the installation manual provided with 
the branch pipe kit.

REQUIREMENT

Be sure to use an insulating material which can 
withstand temperatures above 120°C for the gas 
side pipe since this pipe will become very hot during 
heating operations.

31-EN

32-EN

Summary of Contents for RAV-GM1101AT8JP-E

Page 1: ...English AIR CONDITIONER SPLIT TYPE Installation Manual Outdoor Unit Model name For commercial use RAV GM1101AT8P E RAV GM1101AT8JP E RAV GM1401AT8P E RAV GM1401AT8JP E ...

Page 2: ...destroy the ozone layer This outdoor unit is designed exclusively for use with R32 refrigerant Be sure to use in combination with a R32 refrigerant indoor unit This equipment complies with IEC 61000 3 12 provided that the short circuit power Ssc is greater than or equal to Ssc 1 at the interface point between the user s supply and the public system It is the responsibility of the installer or user...

Page 3: ... the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such op...

Page 4: ...ammable refrigerant If refrigerant leaks and comes in contact with fire or heating part it will create harmful gas and there is risk of fire Read the OWNER S MANUAL carefully before operation Service personnel are required to carefully read the OWNER S MANUAL and INSTALLATION MANUAL before operation Further information is available in the OWNER S MANUAL INSTALLATION MANUAL and the like Warning ind...

Page 5: ...red When installing relocating or servicing the air conditioner use only the specified refrigerant R32 to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines 1 Precautions for safety The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual WARNING General Before starting to in...

Page 6: ...ust this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks Pipe work shall be protected from physical damage Compliance with national gas regulations shall be observed Selection of installation location If you install the unit in a small room take appropriate measures to prevent the refrigerant from exceedin...

Page 7: ...e refrigerant pipe with the service valve left open and the compressor still operating will cause air etc to The appliance shall be installed in accordance with national wiring regulations Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire Use wiring that meets the specifications in the Installation Manual and the stipulations in the local reg...

Page 8: ...it is installed in a small space and refrigerant leaks accumulation of highly concentrated refrigerant may cause a fire hazard Therefore be sure to follow the installation space instructions in the Installation Manual and provide open space on at least one of the four outdoor unit sides In particular when both the discharge and intake sides face walls and obstacles are also placed on both sides of...

Page 9: ...epared tools and equipment must be used exclusively Legend Conventional tools R32 or R410A Prepared newly Use for R32 only Tools equipment Use How to use tools equipment Gauge manifold Vacuuming charging refrigerant and operation check Conventional tools R410A Charging hose Conventional tools R410A Charging cylinder Can not be used Unusable Use the electronic refrigerant charging scale Gas leak de...

Page 10: ...complete grounding can cause an electric shock Do not connect ground wires to gas pipes water pipes lightning rods or ground wires for telephone wires Test run Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during startup CAUTION Incorrect installation work may result in a malfunction or complaints from customers Item Model GM1101 GM1401 5 to 50 ...

Page 11: ...e the discharge air is not blocked 2 When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building secure normal fan operation by using a duct or wind shield 3 When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper stairs or rooftop of a building apply the windproofing...

Page 12: ...o be drained through the drain hose attach the following drain nipple and waterproof rubber cap and use the drain hose Inner dia 16 mm sold on the market Also seal knockout hole and the screws securely with silicone material etc to prevent water from leaking Some conditions may cause dewing or dripping of water When collectively draining discharged water completely use a drain pan For reference If...

Page 13: ...not allowed indoors When mechanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be refabricated 2 Tight connection between pipes and unit 3 Evacuate the air in the connecting pipes by using VACUUM PUMP 4 Check the gas leakage Connected points R32 R410A tool used Refrigerant Piping 1 Use the following items for the refriger...

Page 14: ...i e H m h t g n e l e p i p e l b a w o l l A difference Indoor outdoor H m r e p p U t i n u r o o d n I L h t g n e l l a t o T Outdoor unit Lower 0 3 0 3 0 5 Pipe diameter mm Number of bent portions e d i s d i u q i L e d i s s a G s s e l r o 0 1 5 9 Ø 9 5 1 Ø System Model Allowable pipe length m Height difference m Total length Ɛ1 Ɛ2 Ɛ1 Ɛ3 Ɛ1 Ɛ4 Maximum Distributed pipes Ɛ2 Ɛ3 Ɛ4 Maximum Dis...

Page 15: ... charge port of the set Open Handle Low fully Turn ON the vacuum pump 1 Loosen the flare nut of the packed valve Gas side a little to check that the air passes through 2 Retighten the flare nut Execute vacuuming until the compound pressure gauge indicates 101 kPa 76 cmHg 1 Close Handle Low completely Turn OFF the vacuum pump Leave the vacuum pump as it is for 1 or 2 minutes and check that the indi...

Page 16: ...0 to 25 N m 2 0 to 2 5 kgf m Charge port 14 to 18 N m 1 4 to 1 8 kgf m Flare nut Charge port Valve unit Using a minus screwdriver turn it counterclockwise by 90 until it hits the stopper Full open Groove to insert a screwdriver Handle position Groove position Closed completely Opened fully Fully open the valves of the outdoor unit First fully open the valve on the liquid side and then fully open t...

Page 17: ...Incorrect incomplete wiring may lead to an electrical fire or smoke Prepare an excluVLYe power supply for the air conditioner This product can Ee connected to the mains power Fixed wire connections VZLWFh that disconnects all poles and has a contact separation of at least 3 mm must Ee incorporated in the fixed wiring Be sure to use the cord clamps attached to the product Do not damage or scratch t...

Page 18: ...n compressor failure 4 x 1 5 mm2 or more 1 Remove the mounting screws 2 pieces open the electrical control box cover 2 Connect the power supply wires and system interconnection wires to the terminal block of the electrical control box 3 Tighten the screws of the terminal block connect the wires matching the terminal numbers Do not apply tension to the connecting section of the terminal block 4 Clo...

Page 19: ...nterrupted by the protective device turn off the air conditioner In this case use a refrigerant recovery device 12Air conditioner operating conditions For proper performance operate the air conditioner under the following temperature conditions If air conditioner is used outside of the above conditions safety protection may work 13Functions to be implemented locally Handling existing pipe When usi...

Page 20: ...ck 12 Current detection circuit error 13 Thermostat for compressor activated 14 Model data not set 15 MCU MCU commumication error 16 Discharge temperature error 17 High pressure SW error 18 Power supply voltage error 19 Heat sink overheating error 20 Gas leak detected 21 4 way valve reverse error 22 High pressure release operation 23 Fan system error 24 Drive device short circuiting 25 Position de...

Page 21: ... the thickness is less than 0 7 mm be sure to use new pipes for the refrigerant piping works 3 When the outdoor unit was left with the pipes disconnected or the gas leaked from the pipes and the pipes were not repaired and refilled There is the possibility of rain water or air including moisture entering the pipe 4 When refrigerant cannot be recovered using a refrigerant recovery unit There is the...

Page 22: ...or Nitrogen gas pressure 0 5 MPa Existing pipes Cannot be used Use new pipes Clean the pipes or use new pipes If there is discharge of remains it is judged that a large quantity of remains are present Connect the indoor outdoor units to the existing pipe Use a flare nut attached to the main unit for the indoor outdoor units Do not use the flare nut of the existing pipe Re machine the flare machini...

Page 23: ...4 RAV GM1101AT8JP E 68 74 RAV GM1401AT8P E 68 74 RAV GM1401AT8JP E Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en 0 10 20 30 40 50 60 70 80 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 3 0 M kg Amin m 2 Wall mounted unit Floor standing unit Ceiling mounted unit 43 EN 44 EN ...

Page 24: ...eenhouse gases and any relevant local legislation 6 Periodical inspections for refrigerant leaks may be required depending on European or local legislation 7 Contact dealers installers etc for any questions Fill in the label as follows 1003003201 Pre charged refrigerant at factory kg specified in the nameplate Additional charge on installation site kg GWP kg 1000 Refrigerant Label Contains fluorin...

Page 25: ...ssively Suffocation from leakage of R is almost non existent If a conditioner system is to be installed in a small room select a suitable model and installation procedure so that if the refrigerant accidentally leaks out its concentration does not reach the limit and in the event of an emergency measures can be made before injury can occur In a room where the concentration may exceed the limit cre...

Page 26: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1124251101 ...

Reviews: