Item
Operation flow and applicable data,etc
Description
19
.
Outdoor
control
Quiet
<With Quiet control/Non-select method>
1. Purpose
For the users who concern about noise
of the outdoor unit, this control controls
the max. revolutions of the compressor
to reduce the noise.
2. Description
To reduce noise, [RESET] button of the
indoor unit is kept pushed for 20
seconds.
The number of revolution for the indoor
fan motor and the seup temp value are
kept as they are.
3. Operation
As shown in the table, the maximum
revolution number of indoor unit
compressor can be reduced.
As the maximum number of revolution
of the compressor is restricted, the rise-
up performance at the start time is
weakened.
Select "Conrol" or "No conrol" by keeping
[RESET] button pushed for 20 seconds.
("No control" at shipment from the factory.)
Exchanging from "No control" to "Control" :
Beep sound is heard (Pi, Pi, Pi, Pi, Pi) and
the operation LED 5Hz flashes for 5
seconds.
Exchanging from "Control" to "No control" :
Beep sound is heard.
(Operation LED does not flash.)
<Maximum number of revolution of compressor at normal time and Quiet control time>
RAS-25
J2KVSG-ND
RAS-35
J2KVSG-ND
Quiet controlled
(rps)
COOL
4
7
17
59
20
−5°C ~
100
31
96
31
HEAT
−10 ~ −5°C ~
100
31
96
31
−10°C ~
100
31
96
31
Outside temp.
(TO)
Normal time
(rps)
Normal time
(rps)
Quiet controlled
(rps)
- 45 -