Evacuating
After the piping has been connected to the indoor unit, you can perform the
air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a
vacuum pump. Do not use the refrigerant in the outdoor unit. For details,
see the manual of the vacuum pump.
Using a vacuum pump
Be sure to use a vacuum pump with counter-flow prevention function so that
inside oil of the pump does not flow backward into pipes of the air conditioner
when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R32,
refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to the service port of the
packed valve at gas side.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for
about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters)
(assuming a pump capacity of 27 liters per minute) Then confirm that the
compound pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of the gauge manifold valve.
6. Open fully the valve stem of the packed valves (both gas and liquid sides).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
Pressure gauge
–101 kPa
(–76 cmHg)
Handle Lo
Charge hose
Connecting pipe
Manifold valve
Handle Hi
(Keep full closed)
Charge hose
Vacuum pump adapter for
counter-flow prevention
Packed valve at gas side
Service port (Valve core (Setting pin))
Packed valve at liquid side
Vacuum
pump
CAUTION
• KEEP IMPORTANT 6 POINTS FOR PIPING WORK.
(1) Take away dust and moisture (inside of the connecting pipes).
(2) Tighten the connections (between pipes and unit).
(3) Evacuate the air in the connecting pipes using a VACUUM PUMP.
(4) Check gas leak (connected points).
(5) Be sure to fully open the packed valves before operation.
(6) Reusable mechanical connectors and flared joints are not allowed
indoors. When mechanical connectors are reused indoors, sealing
parts shall be renewed. When flared joints are reused indoors, the
flare part shall be refabricated.
Packed valve handling precautions
• Open the valve stem all the way out, but do not try to open it beyond the
stopper.
Pipe size of Packed Valve
Size of Hexagon wrench
12.70 mm and smallers
A = 4 mm
15.88 mm
A = 5 mm
• Securely tighten the valve cap with torque in the following table:
Cap
Cap Size (H)
Torque
Valve Rod Cap
H17 – H19
14~18 N·m
(1.4 to 1.8 kgf·m)
H22 – H30
33~42 N·m
(3.3 to 4.2 kgf·m)
Service Port Cap
H14
8~12 N·m
(0.8 to 1.2 kgf·m)
H17
14~18 N·m
(1.4 to 1.8 kgf·m)
Hexagon wrench
is required.
Service Port Cap
Valve Rod Cap
10
1122950109_S04_182x257_52p_S_p70_18TR+RU.indd 12
12/25/2018 10:46:56 AM
Summary of Contents for RAS-16TAVG-EE
Page 49: ...MEMO 1122950109_S04_182x257_52p_S_p70_181217_EN TR RU indd 49 12 25 2018 10 47 23 AM ...
Page 50: ...MEMO 1122950109_S04_182x257_52p_S_p70_181217_EN TR RU indd 50 12 25 2018 10 47 23 AM ...
Page 51: ...1122950109_S04_182x257_52p_S_p70_181217_EN TR RU indd 51 12 25 2018 10 47 23 AM ...
Page 52: ...1122950109 1122950109_S04_182x257_52p_S_p70_181217_EN TR RU indd 52 12 25 2018 10 47 23 AM ...