– 24 –
7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19
35/-
10SKVR-E
0.9 to 1.1
12 to 14
37 to 39
High
High
49
13SKV-E
0.8 to 1.0
11 to 13
39 to 41
High
High
77
13SKVR-E
0.8 to 1.0
11 to 13
46 to 48
High
High
63
16SKV-E
0.7 to 0.9
10 to 12
47 to 49
High
High
89
16SKVR-E 0.8 to 1.0 11 to 13 40 to 42 High High 83
condition(°C)
Tempeature
Heat exchanger
pipe temp.
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/-
7/6
10SKVR-E
2.5 to 2.7
39 to 41
0 to 3
High
High
60
13SKV-E
2.7 to 2.9
43 to 45
0 to 2
High
High
80
13SKVR-E
2.6 to 2.8
41 to 43
0 to 2
High
High
66
16SKV-E
2.5 to 2.7
39 to 41
0 to 2
High
High
89
16SKVR-E
2.7 to 2.9
43 to 45
0 to 2
High
High
83
Tempeature
Heat exchanger
condition(°C)
pipe temp.