background image

12

ELECTRICAL WORKS

The power supply can be selected to connect to indoor unit or outdoor unit. Choose proper way and connect the power supply and connecting cable by follow 

the instruction as following.

Model

RAS-10PKVPG-E

RAS-13PKVPG-E

RAS-16PKVPG-E

Power source

50Hz, 220-240 V Single phase

Maximum running current

8.50A

10.00A

10.50A

Circuit breaker rating

10.50A

12.50A

13.50A

Power supply cable

H07RN-F or 60245 IEC66 (1.5 mm

2

 or more)

Connecting cable

Wiring of the cable can be carried out without removing the main panel.

1.  Remove the front panel.

  Pull and lift up front panel until it stops, move arms on left and right side 

to outward direction then pull toward you to remove front panel.

 

w

  Beware front panel fall down that may cause of injure or part damage.

Arm

Arm

2.  Remove the terminal cover and cord clamp.

3.  Insert the cable (according to the local cords) into the pipe hole on the 

wall.

4.  Take out the cable protrudes about 20 cm from the front.

5.  Insert the cable fully into the terminal block and secure it tightly with 

screws.

6.  Tightening torque : 1.2 N·m (0.12 kgf·m)

7.  Secure the cable with the cord clamp.

8.  Fix the terminal cover and attach front panel to the indoor unit.

1.  Remove the valve cover from the outdoor unit.

2.  Connect the cable to the terminals as identified with their respective 

matched numbers on the terminal block of indoor and outdoor unit.

3.  When connecting the cable to the outdoor unit terminals, make a loop as 

shown in the installation diagram of indoor and outdoor unit to prevent 

water coming in the outdoor unit.

4.  Insulate the unused cords (conductors) from any water coming in the 

outdoor unit. Proceed them so that they do not touch any electrical or 

metal parts.

Wiring Connection

     Indoor unit

     Outdoor unit

Carry out attaching in the reverse order to removal.

Keep front panel horizontally and put both arms into guides.

Make sure both arms are inserted completely.

If the gap between main panel and front panel isn’t even, remove and attach 

again.

     How to attach the front panel

•  Be sure to refer to the wiring system diagram labeled inside the main 

panel.

•  Check local electrical cords and also any specific wiring instructions or 

limitations. 

CAUTION

Valve cover

Terminals block

Main panel

Terminal cover

Terminals block

Front panel

about 20 cm

Cable

Front panel

Main panel

Arm

Guide

01_1121451198-EN.indd   12

4/26/2561 BE   10:06 AM

Summary of Contents for RAS-16PKVPG-E

Page 1: ...AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL Indoor unit RAS 10PKVPG E RAS 13PKVPG E RAS 16PKVPG E Outdoor unit RAS 10PAVPG E RAS 13PAVPG E RAS 16PAVPG E 1121451198 ENGLISH R32 ...

Page 2: ...oor unit is fixed to Installation plate with screws 9 n Drainage 9 OUTDOOR UNIT 10 n Installation Place 10 n Precautions about Installation in Regions with Showfall and Cold Temperatures 10 n Refrigerant Piping Connection 10 n Evacuating 11 ELECTRICAL WORKS 12 n Wiring Connection 12 n Power Supply and Connecting Cable Connection 13 n Power supply input Wiring Diagram 14 OTHERS 15 n Gas Leak Test 1...

Page 3: ... incorrect use of this unit may cause severe injury or death CAUTION It indicates that incorrect use of this unit may cause personal injury 1 or property damage 2 1 Personal injury means a slight accident burn or electrical shock which does not require admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources CAUTION This appliance must be co...

Page 4: ...ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE ...

Page 5: ...d possibly result in explosion and injury Thickness of copper pipes used R32 must be more than 0 8mm Never use copper pipes thinner than 0 8mm Do not perform flare connection inside a building or dwelling or room when joining the heat exchanger of indoor unit with interconnection piping Refrigerant connection inside a building or dwelling or room must be made by brazing or welding Joint connection...

Page 6: ...ual carefully before installing the unit It contains further important instructions for proper installation The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installat...

Page 7: ...Vacuum or wash and then dry them 4 Reinstall the air filters and close the air inlet grille ACCESSORY AND INSTALLATION PARTS No Parts name No Parts name 1 Installation plate x 1 2 Wireless remote control x 1 3 Battery x 2 4 Remote control holder x 1 5 Mounting screw ø4 x 25 l x 6 6 Flat head wood screw ø3 1 x 16 l x 2 7 Drain nipple x 1 for heating model only 8 Cap water proof x 2 for some models ...

Page 8: ...it and wall and tilt the indoor unit for better operation The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Do not allow the drain hose to get slack Make sure to run the drain hose sloped downward The flare connection should be installed outdoors Insulate the refrigerant pipes separately with insulation not together 6 mm thick heat resisting p...

Page 9: ...ncrete wall with anchor bolts use the anchor bolt holes as illustrated in the below figure 3 Install the installation plate horizontally in the wall When installing the installation plate with a mounting screw do not use the anchor bolt holes Otherwise the unit may fall down and result in personal injury and property damage 1 After determining the pipe hole position on the mounting plate drill the...

Page 10: ...polyethylene core or the like for bending pipe Use the handle of screwdriver etc Slit Cap Slit NOTE If the pipe is bent incorrectly the indoor unit may unstably be set on the wall After passing the connecting pipe through the pipe hole connect the connecting pipes to the auxiliary pipes and wrap the facing tape around them Do not perform flare connection inside a building or dwelling or room when ...

Page 11: ... extension drain hose insulate the connecting part of extension drain hose with shield pipe NOTE The hole should be made at a slight downward slant on the outdoor side Arrange the drain pipe for proper drainage from the unit Improper drainage can result in dew dropping CAUTION This air conditioner has the structure designed to drain water collected from dew which forms on the back of the indoor un...

Page 12: ...ain water does not raise any problems CAUTION Do not scratch the inner surface of the flared part when removing burrs Flare processing under the condition of scratches on the inner surface of flare processing part will cause refrigerant gas leak CAUTION When the outdoor unit is installed in a place where the drain water might cause any problems Seal the water leakage point tightly using a silicone...

Page 13: ...p 3 Open fully the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 25 meters 15 minutes for 25 meters assuming a pump capacity of 27 liters per minute Then confirm that the compound pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure side valve handle of the gauge manif...

Page 14: ...e 1 2 N m 0 12 kgf m 7 Secure the cable with the cord clamp 8 Fix the terminal cover and attach front panel to the indoor unit 1 Remove the valve cover from the outdoor unit 2 Connect the cable to the terminals as identified with their respective matched numbers on the terminal block of indoor and outdoor unit 3 When connecting the cable to the outdoor unit terminals make a loop as shown in the in...

Page 15: ...e Stripping length of the connecting cable Stripping length of the connecting cable Indoor Unit Indoor Unit Outdoor Unit Outdoor Unit 100 mm 10 mm 10 mm 90 mm Power supply terminal block L N Connecting terminal block 1 2 3 Earth line Connecting cable cord Power supply cord Earth line Connecting cable about 20 cm Plastic wire guide 45 mm 50 mm 10 mm 10 mm Connecting cable connect to terminal block ...

Page 16: ... may cause some electrical part burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3mm must be incorporated in the fixed wiring Power supply input Wiring Diagram Indoor Terminal Block Power supply input O...

Page 17: ...ame room or adjacent two rooms if operating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation betwe...

Reviews: