– 26 –
8-1-8. Outdoor Fan Control (DC Fan Motor)
Although the outdoor fan motor drives the outdoor fan by non-step variable system of the revolution speed, the
revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside
of the room, the operation may be continued as the outdoor fan stops in order to protect the outdoor fan motor.
If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.
<COOL, DRY>
Table 8-1-3
8-2. Description of Operation Circuit
• Turning [ON] the breaker flashes the operation lamp.
This is the display of power-ON (or notification of power failure).
• When pushing [START/STOP] button of the remote control, receive sound is issued from the main unit, and
the next operations are performed together with opening the vertical air flow louvers.
<HEAT>
Table 8-1-4
Model name
RAS-10YAV-E
RAS-13YAV-E
Compressor revolution (rps)
To 13,2
To 34,1
From 34,7
To 13,2
To 34,1
From 34,7
TO
≥
38°C
450
800
800
450
940
940
TO < 38°C
450
630
800
450
700
940
Outdoor temp. sensor
TO
TO < 15°C
390
390
TO
≥
38°C
450
630
800
450
700
940
TO < 38°C
450
450
630
450
450
700
ECONO. operation
TO < 15°C
390
390
TO is abnormal
630
630
800
700
700
940
Model name
RAS-10YAV-E
RAS-13YAV-E
Compressor revolution (rps)
To 16,2
To 44,3
From 44,9
To 16,2
To 44,3
From 44,9
TO
≥
5°C
390
580
800
390
650
900
Outdoor temp. sensor
TO
TO < 5°C
580
580
800
650
650
940
TO
≥
5°C
390
390
580
390
390
650
ECONO. operation
TO < 5°C
390
580
580
390
650
650
TO is abnormal
390
580
800
390
650
900