7-2. Operation Data
<Cooling>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19
35/-
0.9 to 1.1
9 to 11
47 to 49
High
High
54
<Heating>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/-
7/6
2.4 to 2.6
43 to 45
0 to 3
High
High
68
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition 5 m
–
20
–