17
-
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (RAS-13UKHP-E
3
, RAS-10UKHP-E
3, RAS-07UKHP-E3
)
No.
Parts name
Type
Specifications
1 Fan motor (for indoor) SKF-220-20-4A-1 AC Motor with 150 C thermo fuse
2
Thermo sensor (TA-sensor)
10k at 25 C
3
Switching transformer (T01)
SWT-47
4
Microcontroller unit (IC30)
TMP87CM40AN
5
Heat exchanger sensor
10k at 25 C
(TC-sensor)
6
Line filter (L01)
LC*SS11V-06270
27mH, 600mA
7 Bridge rectifier (DB01) D3SBA60 4A, 600 V
8
Capacitor (C02)
KMH400VSSN47M22S
47
m
F, 400 V
9
Fuse (F01)
TSCR6.3A
T6.3A, 250VAC
10
Varistor (R21, R22)
15G561K
560 V
11
Resistor (R01)
RF-2TK5R6
5.6 , 2 W
12
Louver motor
MP24GA
12VDC
13
Relay (Comp., RY01)
DI12D1
Rating 20A/AC250 V, 12VDC
14
Relay (Fan, RY03)
G5N-1A
Rating 3A/AC250 V, 12VDC
15
Relay (Solenoide, RY04)
G5N-1A
Rating 3A/AC250 V, 12VDC
4-2. Outdoor Unit (RAS-13UAH-E
3
)
No.
Parts name
Type
Specifications
Output (Rated) 1100 W, 2 poles, 1 phase, 220
-
240 V, 50Hz
1
Compressor
PH170T2-4L2
Winding resistance ( )
C-R
C-S
(at 20 C)
2.22
3.04
Output (Rated) 42 W, 6 poles, 1 phase, 220
-
240 V, 50Hz
2
Fan motor (for outdoor)
HF-240-42A
Winding resistance ( )
Red-Black
White-Black
(at 20 C)
176.2
290.5
3
Running capacitor
DS451155CBPQC AC 450 V, 1.5
m
F
(for fan motor)
4
Running capacitor
DS371356CPNB AC 370 V, 35
m
F
(for compressor)
5 Overload relay Bi
m
etal of current cantrol
:
RAT00AL
Bi
m
etal of temperature control
:
U/T : 8.6A (100°C), OPEN : 150±5°C, CLOSE : 70±11°C
OPEN : 130±5°C, CLOSE : 75±15°C
W
W
W
W
W
°
°
°
°
°
FILE NO. SVM-04004