Q9 ASD Installation and Operation Manual
My Function Count Data 1
Program
My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT1 (ON Timer).
COUNT1 (ON Timer) outputs a 1 upon reaching the threshold setting at this
parameter.
Direct Access Number — F933
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
My Function Count Data 2
Program
My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT2 (ON Timer).
COUNT2 (ON Timer) outputs a 1 upon reaching the threshold setting at this
parameter.
Direct Access Number — F934
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Input Function Target 1
Program
My Function Unit 4
This parameter plays a role in the setup of the My Function feature by selecting
the functionality of the programmable Input Function Target 1 terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any of the user-selectable functions listed in
, or
.
for more information on this parameter.
Direct Access Number — F935
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Input Function Command 1
Program
My Function Unit 4
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
lists the available selections. Their use and selection
requirements are described in an example at
.
Direct Access Number — F936
Parameter Type — Selection List
Factory Default — 0 (NOP)
Input Function Target 2
Program
My Function Unit 4
This parameter plays a role in the setup of the My Function feature by selecting
the functionality of the programmable Input Function Target 2 terminal.
This setting assigns the function of the programmable Input Function Target 2
terminal to any of the user-selectable functions listed in
, or
.
for more information on this parameter.
Direct Access Number — F937
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Input Function Command 2
Program
My Function Unit 4
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
lists the available selections. Their use and selection
requirements are described in an example at
.
Direct Access Number — F938
Parameter Type — Selection List
Factory Default — 0 (NOP)