Q9 ASD Installation and Operation Manual
149
Command Mode/Frequency Mode Change Lockout
No Path — Direct Access Only
This parameter Enables/Disables the ability to change the Command Mode and
the Frequency Mode settings on the panel during Run.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F736
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Yes
Lockout All Keys
No Path — Direct Access Only
This parameter Enables/Disables EOI keypad operation. Select Locked to disable
all keypad entries.
Cycle the power to the ASD to activate the changes made to this parameter.
To unlock EOI keypad for normal operation, press and hold the Rotary Encoder
for (greater than) 5 seconds. This unlocks the keypad for the current session
ONLY. Upon a trip or power off, the Locked status of this parameter setting will
be re-asserted and the keypad will be locked out.
This setting may also be changed via communications.
Settings:
0 — Unlocked
1 — Locked
Direct Access Number — F737
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Yes