Q9 ASD Installation and Operation Manual
Electronic Thermal Protection 1
Program
Motor Settings
This parameter specifies the motor overload current level for motor number 1.
This value is entered as either a percentage of the full load rating of the ASD or as
a percentage of the FLA of the motor.
The unit of measurement for this parameter may be set to A/V (Amps) or it may
be set as a percentage of the ASD rating. The name-plated FLA of the motor may
be entered directly when Amps is selected as the unit of measurement (see
to change the display unit).
Electronic Thermal Protection 1 settings will be displayed in Amps if the EOI
display units are set to A/V rather than %.
Direct Access Number — F600
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 100.0
Units — % (or
setting)
Over-Current Stall Level
Program
Protection
This parameter specifies the output current level at which the output frequency is
reduced in an attempt to prevent a trip. The over-current level is entered as a
percentage of the maximum rating of the drive.
Note:
The Motor Overload Protection parameter must enabled at
to use this feature.
Direct Access Number — F601
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 10
Maximum — 165
Units — %
Trip Save at Power Down
Program
Protection
This parameter Enables/Disables the Trip Save setting. When enabled, this
feature logs the trip event and retains the trip information when the system powers
down. The trip information may be viewed from the Monitor screen.
When disabled, the trip information will be cleared when the system powers
down.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F602
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Emergency Off Mode Selection
Program
Protection
This parameter determines the method used to stop the motor in the event that an
Emergency Off command is received and the system is configured to use this
feature.
This setting may also be associated with the FL terminals to allow the FL relay to
change states when an EOFF condition occurs by setting the FL terminal to Fault
FL (all) (see
).
Note:
A supplemental emergency stopping system should be used with the
ASD. Emergency stopping should not be a task of the ASD alone.
Settings:
0 — Coast Stop
1 — Deceleration Stop
2 — DC Injection Braking Stop
Direct Access Number — F603
Parameter Type — Selection List
Factory Default — Coast Stop
Changeable During Run — No
Emergency Off