Q9 ASD Installation and Operation Manual
BIN Reference 2
Program
Frequency Settings
This parameter is used to set the speed of the BIN input terminals when the BIN
terminals are used as the control input.
This parameter sets the BIN input signal that is associated with
This value is entered as 0% to +100% of the BIN input signal range.
See BIN Reference 1 (
) for further information on this setting.
Direct Access Number — F230
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
BIN Frequency 2
Program
Frequency Settings
This parameter is used to set the speed of the BIN input terminals when the BIN
terminal are used as the control input.
and is the frequency that is associated with
See BIN Reference 1 (
) for further information on this setting.
Direct Access Number — F231
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Maximum — 0.00
Maximum — Max. Freq. (
Units — Hz
PG Reference 1
Program
Frequency Settings
This parameter is used to set the gain and bias of the PG input terminal of the
option board when a shaft-mounted encoder is used as the control input while
operating in the Speed Control mode.
Note:
See the PG Option Board Instruction Manual P/N 58687 for more
information.
PG Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at
the PG input terminal:
• Program
Utility Group
Command Mode
Option Board.
• Program
Utility Group
Frequency Mode 1
Pulse (Option).
• Provide a Run command (F and/or R).
Speed Control
Perform the following setup to allow the system to perform Speed control from
the PG input terminals:
• Set
).
• Set the PG input value (
) that represents
• Set
).
• Set the PG input value (
) that represents
Once set, as the PG input pulse count rate changes, the output frequency of the
ASD will vary in accordance with the above settings.
This parameter sets the PG input pulse count that represents
. The
range of values for this parameter is 0% to 100% of the PG input pulse count
range.
Note:
Further application-specific PG settings may be performed from
the following path: Program
Feedback Setting
PG Settings
.
Direct Access Number — F234
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0
Maximum — 100.0
Units — %
Frequency Settings