Meets or Exceeds
Q9 Standard Specifications
Input Voltage
230 V
HP Rating
1
2
3
5
7.5
10
15
20
25
30
40
50
60
Current Rating
4.8
7.8
11
17.5
25.3
32.2
48.3
62.1
78.2
92
120
150
177
Input Voltage
460 V, 50/60 Hz, Three-Phase
HP Rating
1
2
3
5
7.5
10
15
20
25
30
40
50
60
Current Rating
2.1
3.4
4.8
7.6
11
14
21
27
34
40
52
65
77
HP Rating
75
100
125
150
200
250
300
350
400
Current Rating
96
124
156
180
240
302
361
414
477
Power Requirements
Input Voltage Range
200 to 240 V, 50/60 Hz, Three-Phase
380 to 480 V, 50/60 Hz, Three-Phase
Power Terminals
Input (L1/R, L2/S, L3/T), Output (T1/U, T2/V, T3/W), DCL (PO, PA), DC Bus (PA, PC)
Voltage Tolerance
±10%
Frequency Tolerance
±2%
Control Specifications
Output Method
Sine Wave Pulse-Width Modulated System
Output Frequency Range
0 to 299 Hz
V/Hz Pattern
Constant Torque, Variable Torque, Automatic Torque Boost, Sensor-Less Vector Control (Speed), V/f Five-Point Setting,
Permanent Magnet Control, Auto Power-Saver
Overload Current Rating
100% Continuous; 110% for One Minute
Frequency Control
Rotary Encoder Integrated Into EOI, 0 to 10 VDC, ±10 VDC, 4 to 20 mA, Binary Input, Motor Operated Potentiometer
Frequency Accuracy
Analog Input: ±0.2% of Maximum Output Frequency; Digital Input: ±0.01% of ±0.022 Hz of Output Frequency
Frequency Resolution
Operation Panel: 0.01 Hz
Acceleration/Deceleration
0.1 to 6000 Seconds
Analog Inputs
Three: One Isolated Input Selectable Between 0 to 10 VDC/4 to 20 mA, One 0 to 10 VDC, and One ±10 VDC
Analog Outputs
Two Programmable to 57 Functions (One Switchable 0 to 10 VDC/0 to 20 mA, and One 0 to 1 mA)
Discrete Inputs
Eight Programmable to 41 Functions
Sink/Source Switching
Ability to Switch Between Sink Logic and Source Logic
Discrete Outputs
Three Programmable to 83 Functions (Two Form-A and One Form-C); Outputs Rated at 2 A/120 VAC, 2 A/30 VDC
PID (Set Point Control)
Adjustment of Proportional Gain, Integral Time, Differential Time, and Delay Filter
Braking Control
DC Braking, Over-Flux Braking
Communication Ports
Two-Wire/Four-Wire RS485
Communication Protocol
BACNet
®
, LonWorks
®
, Metasys N2
®
, Modbus RTU
®
, APOGEE FLN
®
Protection
Protective Functions
Overvoltage Stall, Overcurrent Stall, Critical (Skip) Frequencies, Ride-Through, Electronic Thermal Motor Protection
Interrupting Current Rating 100,000 AIC
Faults
Overcurrent, ASD Overheat, ASD Overload, Motor Overload, Overvoltage, Overtorque, Undercurrent, Ground Fault,
Communication Time-Out, Analog-Input Terminal Overvoltage, Emergency Stop, Input/Output Phase Loss, RAM/ROM
Error, Undervoltage
Retry
Ability to Reset Certain Faults Automatically; Programmable Up to 10 Retries
Restart
Ability to Detect Speed and Direction of Freewheeling Motor and Start into Motor Smoothly
Interface
EOI Display
Full-English Backlit LCD Display
Keys
LOCAL/REMOTE, ESC, RUN, MODE, STOP/RESET
Rotary Encoder
Encoder with Integrated Enter Key for Frequency and Parameter Adjustments
Monitoring
Monitors 19 Drive Conditions
Display Units
Programmed to Display Percentage or Volts/Amps
Ambient Conditions
Temperature
-10˚ to 40˚C
Relative Humidity
Maximum 93% (Non-Condensing)
Altitude
1000 Meters or Less
Q9 Dimensions
230 V
1 to 2 HP
3 to
5 HP
7.5 HP
10 HP
15 to
20 HP
25 to
30 HP
-
40 to
60 HP
-
100 HP
125 HP
-
-
-
460 V
1 to 3 HP
5 to
7.5 HP
10 HP
15 to
20 HP
25 to
30 HP
40 HP
50 to
60 HP
-
75 to
125 HP
150 HP
200 HP 250 HP
300 to
350 HP
400 HP
Frame
2
3
4
5A
5B
6
7A
7B
8
9B
10B
11B
12B
13A
Height (in.)
10.0
11.1
12.6
12.6
15.7
16.5
21.7
21.7
24.8
36.2
40.2
46.9
46.9
46.9
Width (in.)
5.1
6.1
6.9
8.3
9.1
9.4
9.4
12.6
12.6
12.2
13.8
13.0
16.9
23.0
Depth (in.)
6.0
6.5
6.5
7.5
7.5
8.3
8.3
9.5
11.4
14.6
14.6
14.6
14.6
14.6
Your Specifications