93
Preset Speed #13
Program
⇒
Preset Speeds
⇒
Preset Speed #13
This parameter assigns an output frequency to binary number 1101 and is
identified as Preset Speed #13. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #14
Program
⇒
Preset Speeds
⇒
Preset Speed #14
This parameter assigns an output frequency to binary number 1110 and is
identified as Preset Speed #14. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed #15
Program
⇒
Preset Speeds
⇒
Preset Speed #15
This parameter assigns an output frequency to binary number 1111 and is
identified as Preset Speed #15. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
for
further information on this parameter).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit
Maximum — Upper Limit
Units — Hz
Preset Speed Mode Control
Program
⇒
Preset Speeds
⇒
PS Spd Mode Ctrl
Enables/Disables the use of the Preset Speed Mode control for Preset Speeds
1 – 15.
The Preset Speed Mode control setting determines if the speed setting only is
used (disabled) or if (enabled) stored combinations of the Torque, Speed,
Accel/Decel, and Direction settings will be used while running a given Preset
Speed.
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Proportional (P) Gain
Program
⇒
Feedback Settings
⇒
Prop Gain
This parameter determines the degree that the Proportional function affects the
output signal when using PID feedback to control the ASD output. The larger
the value entered here, the quicker the ASD responds to changes in feedback.
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.0