74
Q7 ASD Installation and Operation Manual
LOD Restart Delay Time
Program
⇒
PID Setup
⇒
LOD Restrt Delay
The Low Output Disable Restart Delay Time sets the time that, once expired
and all standard ASD requirements are met, normal ASD operation resumes.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
LOD Start Level
Program
⇒
PID Setup
⇒
LOD Start Level
The Low Output Disable Start Level sets the output frequency threshold that,
if exceeded, will initiate the LOD function if properly configured.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq.
Units — Hz
Low Signal Frequency
Program
⇒
Output Terminals
⇒
Low Signal Freq
This parameter sets the low-speed trip threshold.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Upper Limit
Units — Hz
Main EEPROM Version
Program
⇒
Utility Group
⇒
Main EEPROM VER
This is a read-only parameter that displays the Main EEPROM version.
Maximum Output Frequency
Program
⇒
Fundamental #1
⇒
Max Output Freq
This setting determines the absolute maximum frequency that the ASD can
output. This setting is also referred to as FH.
Accel/decel times are calculated based on the Maximum Frequency setting.
Note: This setting may not be lower than the Upper Limit setting.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — No
Minimum — 30.0
Maximum — 299.0
Units — Hz