62
Q7 ASD Installation and Operation Manual
(Electronic) Thermal Protection #1
Program
⇒
Motor Settings
⇒
Therm Prot #1
This parameter specifies the motor overload current level for motor set #1. This
value is entered as either a percentage of the full load rating of the ASD or as
the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it may be set
as a percentage of the ASD rating. The name-plated FLA of the motor may be
entered directly when Amps is selected as the unit of measurement (see
Program
⇒
Utility Group
⇒
Units for V/I to change the display unit).
Thermal Protection settings will be displayed in Amps if the keypad display
units are set to V/I rather than %.
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %
(Electronic) Thermal Protection #2
Program
⇒
Motor Settings
⇒
Therm Prot #2
This parameter specifies the motor overload current level for motor set #2. This
value is entered as either a percentage of the full load rating of the ASD or as
the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it may be set
as a percentage of the ASD rating. The name-plated FLA of the motor may be
entered directly when Amps is selected as the unit of measurement (see
Program
⇒
Utility Group
⇒
Units for V/I to change the display unit).
Thermal Protection settings will be displayed in Amps if the keypad display
units are set to V/I rather than %.
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %
(Electronic) Thermal Protection #3
Program
⇒
Motor Settings
⇒
Therm Prot #3
This parameter specifies the motor overload current level for motor set #3. This
value is entered as either a percentage of the full load rating of the ASD or as
the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it may be set
as a percentage of the ASD rating. The name-plated FLA of the motor may be
entered directly when Amps is selected as the unit of measurement (see
Program
⇒
Utility Group
⇒
Units for V/I to change the display unit).
Thermal Protection settings will be displayed in Amps if the keypad display
units are set to V/I rather than %.
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %
(Electronic) Thermal Protection #4
Program
⇒
Motor Settings
⇒
Therm Prot #4
This parameter specifies the motor overload current level for motor set #4. This
value is entered as either a percentage of the full load rating of the ASD or as
the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it may be set
as a percentage of the ASD rating. The name-plated FLA of the motor may be
entered directly when Amps is selected as the unit of measurement (see
Program
⇒
Utility Group
⇒
Units for V/I to change the display unit).
Thermal Protection settings will be displayed in Amps if the keypad display
units are set to V/I rather than %.
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %