52
Q7 ASD Installation and Operation Manual
BIN Speed Frequency #2
Program
⇒
Freq Settings
⇒
BIN Speed Ref 2
This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Speed Control mode.
See
for further information on this setting.
This parameter sets BIN Speed Frequency #2 and is the frequency that is
associated with the setting of BIN Speed Reference 2.
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
BIN Speed Reference #1
Program
⇒
Freq Settings
⇒
BIN Speed Ref 1
This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Speed Control or the Torque Control mode.
See
for further information on this setting when used
for Speed control.
See
for further information on this setting when
used for Torque control.
This parameter sets the BIN input that is associated with BIN Speed
Frequency #1 when operating in the Speed control mode or is associated with
the BIN Torque Reference #1 when operating in the Torque control mode.
This value is entered as 0 to 100% of the binary input word 11111111 (255
D
).
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
BIN Speed Reference #2
Program
⇒
Freq Settings
⇒
BIN Speed Freq 2
This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Speed Control or the Torque Control mode.
See
for further information on this setting when used
for Speed control.
See
for further information on this setting when
used for Torque control.
This parameter sets the BIN input that is associated with BIN Speed
Frequency #2 when operating in the Speed control mode or is associated with
the BIN Torque Reference #2 when operating in the Torque control mode.
This value is entered as 0 to 100% of the binary input word 11111111 (255
D
).
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.0
Units — %