P9 ASD Installation and Operation Manual
113
RR Input Point 1 Rate
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Torque
Control
mode.
RR Input Torque Control Setup
Perform the following setup to allow the system to receive
Torque Control
input at the
RR
input terminal:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
RR
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Block
.
Torque Control
Perform the following setup to allow the system to perform
Torque Control
from the
RR
input terminal:
• Set
RR Input Point 1 Rate
).
• Set
RR Input Point 1 Setting
(
) — the input analog signal level that
corresponds to the torque setting at
RR Input Point 1 Rate
.
• Set
RR Input Point 2 Rate
).
• Set
RR Input Point 2 Setting
(
) — the input analog signal level that
corresponds to the frequency setting at
RR Input Point 2 Rate
.
• Provide a
Run
command (F and/or R).
Torque Control is accomplished by establishing an associated
V/f
output pattern
for a given
RR
input level.
Once set, as the
RR
input voltage changes, the output torque of the ASD will
vary in accordance with the above settings.
This parameter sets
RR Input Point 1 Rate
and is the output torque value that
is associated with the setting of
RR Input Point 1 Setting
when operating in
the
Torque Control
mode.
This value is entered as 0% to 250% of the rated torque.
Direct Access Number — F214
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
RR Input Point 2 Rate
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Torque
Control
mode.
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RR
input level.
This parameter sets
RR Input Point 2 Rate
and is the output torque value that
is associated with the setting of
RR Input Point 2 Setting
when operating in
the
Torque Control
mode.
This value is entered as 0% to 250% of the rated torque.
See
RR Input Point 1 Rate
) for additional information on this
parameter.
Direct Access Number — F215
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %