44
Check of HPS
Infinity
Yes
No
1. Disconnect the connector CN681.
2. Check the resistance of HPS 1 minute after the outdoor unit breaker was turned OFF.
Check the resistance between
each terminal.
Reconnect CN681.
Turn ON the breaker to the indoor and the outdoor units.
3 minutes later, start EMERGENCY OPERATION.
Is HPS protection displayed
immediately after compressor
starts?
Replace HPS.
Replace the outdoor control P.C. board.
Normal
• When the operation frequency does not go up from lowest frequency.
MXZ-3DM50VA
CN681
Outdoor control P.C. board
OBH739A