![Toshiba MMU-UP0091HP-E Installation Manual Download Page 19](http://html.mh-extra.com/html/toshiba/mmu-up0091hp-e/mmu-up0091hp-e_installation-manual_1134804019.webp)
– 18 –
EN
ID
ID
2
Each time [ ] [ ] setting button is
pushed, indoor unit numbers in the group
control change cyclically. Select the indoor
unit to change settings for.
•
The fan of the selected indoor unit runs.
The indoor unit can be con
fi
rmed for which
to change settings.
3
Push OFF timer button to con
fi
rm the
selected indoor unit.
Set data
Code No.
4
Push the menu button to make Code No.
[
]
fl
ash. Change Code No. [
] with
[ ] [ ] setting button.
5
Push the menu button to make Set data
[
]
fl
ash. Change Set data [
]
with [ ] [ ] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
•
To change other settings of the selected indoor
unit, repeat from Procedure
4
.
7
When all the settings have been
completed, push ON/OFF button to
determine the settings.
“
” flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “
” is flashing.)
•
To change settings of another indoor unit,
repeat from Procedure
1
.
Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high-ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
For the CODE No. in Procedure
4
, specify [5d].
Select the SET DATA for Procedure
5
from the
“Height list of ceiling possible to be installed” table in
this manual.
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the receiver section P.C. board.
For details, refer to the manual of the wireless remote
controller kit. The settings can also be changed with
the switch on the indoor microcomputer P.C. board.
* Once the setting is changed, setting to 0001 or 0003
is possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of CODE No. [5d] to “
0000
”.
SET DATA
SW501-1
SW501-2
0000
(Factory default)
OFF
OFF
0001
ON
OFF
0003
OFF
ON
MCU(IC501)
SW501-2
SW501-1
Change of lighting time of
filter sign
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
For the CODE No. in Procedure
4
, specify [01].
For the SET DATA in Procedure
5
, select the SET
DATA of filter sign lighting time from the following
table.
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
For the CODE No. in Procedure
4
, specify [06].
For the SET DATA in Procedure
5
, select the SET
DATA of shift value of detection temperature to be
set up from the table below.
SET DATA
Filter sign lighting time
0000
None
0001
150 H
0002
2500 H (Factory default)
0003
5000 H
0004
10000 H
SET DATA
Detection temp shift value
0000
No shift
0001
+1 °C
0002
+2 °C (Factory default)
0003
+3 °C
0004
+4 °C
0005
+5 °C
0006
+6 °C
■
How to set up swing type
The swing type of the louver can be selected.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
•
Specify
[F0]
for the CODE No. in Procedure
4
.
•
Select the following data for the SET DATA in
Procedure
5
.
Swing SET DATA
Swing of louvers
0001
Standard swing
(Factory default)
0002
Dual swing
0003
Cycle swing
•
About “Dual swing”
“Dual” means that louvers
01
and
03
are directed
and swing in one direction and louvers
02
and
04
are directed and swing in the opposite direction.
(When louvers
01
and
03
are directed downward,
louvers
02
and
04
are directed horizontally.)
•
About “Cycle swing”
The four louvers swing independently at respective
timings.
CAUTION
Do not set the swing SET DATA to “
0000
”.
(This setting may cause a failure of the louvers.)
■
How to set up louver lock
(No swing)
A position of the individual louvers (four directions) can
be locked.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
•
Specify
[F1]
,
[F2]
,
[F3]
or
[F4]
for the CODE No. in
Procedure
4
.
•
Select the following data for the SET DATA in
Procedure
5
.
(1)
0001
(2)
0002
(3)
0003
(5)
0005
(4)
0004
SET DATA
* When (4) or (5) is selected, dew drop may occur
during cooling mode.
•
When the setting has been determined, lights up.
35-EN