– 19 –
37-EN
38-EN
9
Applicable controls
REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatic address
setup
It takes up to 10 minutes (usually about 3 minutes) for
the outdoor unit to start operating after the power has
been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default).
If necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a
wireless remote controller, simple remote controller
or group control remote controller by itself so install
a wired remote controller separately as well.
■
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU11-E
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
Set only the Code No. shown in the following table:
Do NOT set any other Code No.
If a Code No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with
the product may result.
1
Push and hold menu button and
[ ] setting button simultaneously for
10 seconds or more.
•
After a while, the display
fl
ashes as shown
in the
fi
gure. “ALL” is displayed as indoor
unit numbers during initial communication
immediately after the power has been
turned on.
Indoor unit No.
2
Each time [ ] [ ] setting button is
pushed, indoor unit numbers in the group
control change cyclically. Select the indoor
unit to change settings for.
•
The fan of the selected indoor unit runs.
The indoor unit can be con
fi
rmed for which
to change settings.
3
Push OFF timer button to con
fi
rm the
selected indoor unit.
Set data
Code No.
4
Push the menu button to make Code No.
[
]
fl
ash. Change Code No. [
] with
[ ] [ ] setting button.
5
Push the menu button to make Set data
[
]
fl
ash. Change Set data [
]
with [ ] [ ] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
•
To change other settings of the selected indoor
unit, repeat from Procedure
4
.
7
When all the settings have been
completed, push ON/OFF button to
determine the settings.
“
” flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “
” is flashing.)
•
To change settings of another indoor unit,
repeat from Procedure
1
.
(Factory default)
SET DATA
External static pressure
0000
30 Pa
0001
50 Pa
0002
40 Pa
0003
80 Pa
0004
65 Pa
0005
100 Pa
0006
150 Pa
—
—
—
—
—
—
(Factory default)
SET DATA
External static pressure
0000
40 Pa
0001
50 Pa
0002
30 Pa
0003
80 Pa
0004
65 Pa
0005
100 Pa
0006
150 Pa
—
—
—
—
—
—
(Factory default)
SET DATA
External static pressure
0000
50 Pa
0001
30 Pa
0002
40 Pa
0003
80 Pa
0004
65 Pa
0005
100 Pa
0006
150 Pa
—
—
—
—
—
—
To set the external static pressure, refer to the
“Fan characteristics” in 6 Duct design.
External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• Specify [5d] to the CODE No. in procedure
4
.
• For the SET DATA of procedure
5
, select a SET
DATA of the external static pressure to be set up
from the following table.
The list above is when SW501-1 and SW501-2 is OFF.
If the setting is wrong, "P12" may appear indicating a
fan motor error.
UP005 to 018
UP024 to 030
UP036 to 056