Test run
11
Maintenance
Before test run
y
Before turning on the power supply, carry out the
following procedure.
1) By using 500 V-megger, check that resistance of
1 M
Ω
or more exists between the terminal block L
to N and the earth (grounding).
If resistance of less than 1 M
Ω
is detected, do not
run the unit.
2) Check the valve of the outdoor unit being opened
fully.
y
To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
y
Do not press the electromagnetic contactor to
forcibly perform a test run. (This is very dangerous
because the protective device does not work.)
y
Before starting a test run, set addresses by following
the Installation Manual supplied with the outdoor
unit.
Execute a test run
y
When a fan operation is to be performed for an
individual indoor unit, turn off the power, short CN72
on the circuit board, and then turn the power back
on. (First set the operating mode to “fan,” and then
operate.) When the test run has been performed
using this method, do NOT forget to release the
shorting of CN72 after the test run is completed.
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner’s Manual to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by thermostat-
OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than
the test run because it applies an excessive load to
the devices.
Wired remote controller
2, 4
3
1,5
1
Push button for 4 seconds or more.
[TEST] is displayed on the display part and
the selection of mode in the test mode is
permitted.
2
Push
button.
3
Select the operation mode with
button, [ Cool] or [ Heat].
y
Do not run the air conditioner in a mode other
than [ Cool] or [
Heat].
y
The temperature controlling function does not
work during test run.
y
The detection of error is performed as usual.
4
After the test run, push
button to
stop a test run.
(Display part is same as procedure
1
.)
5
Push button to cancel (release from) the
test run mode.
([TEST] disappears on the display and the status
returns to a normal.)
CAUTION
When connecting a return air duct to the unit, the cleaning method of the air
fi
lter differs according to the
construction of duct end. Ask a quali
fi
ed installer or quali
fi
ed service person.
<Daily maintenance> (Once every 3 months)
q
Cleaning of the air
fi
lter
(sold separately : TCB-LK2801DP-E)
If displayed on the remote controller, maintain the air
fi
lter
(sold separately).
3
1,2
1
Push the
button to stop the operation,
then turn off the circuit breaker.
1. Take out the air
fi
lter (sold separately).
2. Cleaning with water or vacuum cleaner.
y
If dirt is heavy, clean the air
fi
lter by tepid water with neutral detergent or water.
y
After cleaning with water, dry the air
fi
lter suf
fi
ciently in a shade place.
3. Mount the air
fi
lter (sold separately).
2
Turn on the circuit breaker, then push the
button on the remote controller to start the
operation.
3
After cleaning, push .
display disappears.
CAUTION
y
Do not start the air conditioner while leaving air
fi
lter (sold separately) removed.
y
Push the
fi
lter reset button. ( indication will be turn off.)