– 43 –
*1 Only a part of indoor unit types is installed with the discharge temperature sensor. This temperature is not displayed for other types.
*2 When the units are connected to a group, data of the header indoor unit only can be displayed.
*3 The first digit of an CODE No. indicates the outdoor unit number.
*4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1 , 5 ... U1 outdoor unit (Header unit)
2 , 6 ... U2 outdoor unit (Follower unit 1)
*5 Only the CODE No. 5* of U1 outdoor unit (Header unit) is displayed.
CODE No.
Data name
Display format
Unit
Remote controller display example
U1
U2
Outdoo
r u
n
it in
dividual d
a
ta 1
*
3
10
20
High-pressure sensor detention pressure (Pd)
×10
psi
[4350]=435psi
11
21
Low-pressure sensor detention pressure (Ps)
×10
psi
12
22
Compressor 1 discharge temperature (Td1)
×1
˚F
[0075]=75˚F(24˚C)
13
23
Compressor 2 discharge temperature (Td2)
×1
˚F
14
24
Compressor 3 discharge temperature (Td3)
×1
˚F
15
25
Suction temperature (TS)
×1
˚F
16
26
Outdoor coil temperature 1 (TE1)
×1
˚F
17
27
Outdoor coil temperature 2 (TE2)
×1
˚F
18
28
Temperature at liquid side (TL)
×1
˚F
19
29
Outside ambient temperature (TO)
×1
˚F
1A
2A
PMV1 + 2 opening
×1
pls
[0500] =500pulse
1B
2B
PMV4 opening
×1
pls
1C
2C
Compressor 1 current (I1)
×10
A
[0135]=13.5A
1D
2D
Compressor 2 current (I2)
×10
A
1E
2E
Compressor 3 current (I3)
×10
A
1F
2F
Outdoor fan current (IFan)
×10
A
CODE No.
Data name
Display format
Unit
Remote controller display example
U1
U2
Ou
td
oor unit
individ
ual dat
a 2
*
4
50
60
Compressor 1 revolutions
×10
rps
[0642]=64.2rps
51
61
Compressor 2 revolutions
×10
rps
52
62
Compressor 3 revolutions
×10
rps
53
63
Outdoor fan mode
×1
mode
[0058]= 58 mode
54
64
Compressor IPDU 1 heat sink temperature
×1
˚F
[0075]=75˚F(24˚C)
55
65
Compressor IPDU 2 heat sink temperature
×1
˚F
56
66
Compressor IPDU 3 heat sink temperature
×1
˚F
57
67
Outdoor fan IPDU heat sink temperature
×1
˚F
58
-
Heating/cooling recovery controlled
*
5
0: Normal
1: Recovery controlled
[0010]=Heating recovery controlled
[0001]=Cooling recovery controlled
59
-
Pressure release
*
5
0: Normal
1: Release controlled
[0010]=Pressure release controlled
5A
5B
-
-
Discharge temperature release
*
5
[0001]=Discharge temperature release controlled
Follower unit release
(U2/U2/U4 outdoor units)
*
5
[0100]=U2 outdoor unit release controlled
[0010]=U3 outdoor unit release controlled
[0001]=U4 outdoor unit release controlled
5F
6F
Outdoor unit capacity
×10
ton
[0080]=8ton
CODE No.
Data name
Display format
Unit
Remote controller display example
Indoo
r u
n
it
d
a
ta
*
2
00
Room temperature (During control)
×1
˚F
[0075]=75˚F(24˚C)
[0081]=71˚F(27˚C)
01
Room temperature (Remote controller)
×1
˚F
02
Indoor suction temperature (TA)
×1
˚F
03
Indoor coil temperature (TCJ)
×1
˚F
04
Indoor coil temperature (TC2)
×1
˚F
05
Indoor coil temperature (TC1)
×1
˚F
06
Indoor discharge temperature (TF)
*
1
×1
˚F
08
Indoor PMV opening
×1/10
pls
[0150]=1500pulse
Syst
em dat
a
0A
No. of connected indoor units
×1
unit
[0024]=24 units
0B
Total capacity of outdoor units
Total capacity of connected indoor units
×10
ton
[0215]=21.5ton
0C
No. of connected outdoor units
×1
unit
[0002]=2 units
0D
×10
ton
[0160]=16ton