6
Installation space
Reserve space required for maintenance the indoor unit and service work.
700mm *1
700mm *1
Electric parts box
Ceiling opening size C
Air outlet
400mm (Min.)
Air filter
Ceiling opening
size D
Electric parts box
450mm
Air outlet
Check port B
450mm
Check port A
Air filter
700mm for maintenance of air filter
700mm for
maintenance of air filter
25mm
Ceiling opening part
(150mm)
300mm
Notes)
*1 Be sure that space with 700mm or more is
reserved for attachment/detachment at the
taking-out direction of the air filter.
*2 Be sure to set a check port (A) for the
refrigerant piping, drain piping, maintenance of
drain pan, etc; otherwise maintenance for
devices is unavailable.
*3 If the taking-out direction of the air filter is set at
the left side, be sure to set a check port (B) at the
left side of the set for attachment/detachment of
the air filter. If there is no check port (B), the air
filter cannot be attached or detached.
*4 Be sure to set a ceiling opening for
maintenance of the electric ports such as fan
motor; otherwise maintenance for electric parts
such as fan motor is unavailable.
[Reference] Dewing test conditions
Indoor side: 27°C dry bulb temperature
24°C wet bulb temperature
Air volume: Low air volume, operation time 4 hours
Installation under high-humidity atmosphere
In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere
(dew-point temperature: 23°C or higher).
1. Installation to inside of the ceiling with tiles on the roof
2. Installation to inside of the ceiling with slated roof
3. Installation to a place where inside of the ceiling is used for pathway to intake the outside air
• In the above cases, additionally attach the thermal insulator (Glass wool, etc.) to all positions of the air
conditioner, which come to contact with the high-humidity atmosphere. In this case, arrange the side plate
(Service plate) so
that it is easily removed.
• Apply also a sufficient thermal
insulation to the duct and connecting
part of the duct.
MODEL MMD-AP
Set width (mm)
Air filter width (mm)
Ceiling opening size C
Ceiling opening size D
0071BH to 0121BH
0151BH to 0181BH
0241BH to 0301BH
0361BH to 0561BH
550
700
1000
1350
508
655
960 (480
∗
2)
1310 (655
∗
2)
600
750
1050
1400
470
470
470
470
2
SELECTION OF INSTALLATION PLACE