– 16 –
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3
Specify CODE No. [
] with “TEMP.”
/
buttons.
4
Select SET DATA [
] with “TIME”
/
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
2
.
• To change other settings of the selected indoor
unit, repeat from Procedure
3
.
• Use
button to clear the settings. To make
settings after
button was pushed, repeat
from Procedure
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes
and then the display content disappears and
the air conditioner enters the normal stop
mode.
(While
is flashing, no operation of the
remote controller is accepted.)
External static pressure
settings
<Change on wired remote controller>
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• Specify [5d] to the CODE No. in procedure
3
.
• For the SET DATA of procedure
4
, select a SET
DATA of the external static pressure to be set up
from the following table.
The list above is when SW501-1 and SW501-2 is OFF.
If the setting is wrong, "P12" may appear indicating a
fan motor error.
SET DATA
External static pressure
0000
40 Pa
AP024 to 030
(Factory default)
0001
30 Pa
AP007 to 018
(Factory default)
0002
65 Pa
—
0003
50 Pa
AP036 to 058
(Factory default)
0004
80 Pa
—
0005
100 Pa
—
0006
120 Pa
—
<Setting up on the circuit board of the indoor unit>
To set up the external static pressure, use the DIP switch on the circuit board of the wireless reception part.
For details, refer to the instruction manual of the wireless remote controller kit. Alternatively, use the switch on the
indoor micro computer circuit board as shown in the following figure and table.
SW501
SW501-1
OFF
ON
OFF
ON
SW501-2
OFF
OFF
ON
ON
SET DATA
Factory
default
0001
0003
0006
To reset to the factory default
Switch off SW501-1 and SW501-2, connect a separately-sold
wired remote controller, and then perform the procedure for
installing a separately-sold filter on this page to set the [5d] data
to "0000".
31-EN
32-EN
Summary of Contents for MMD-AP0076BH-E
Page 28: ...EH99892399 ...