Troubleshooting
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit
by checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every dip switch to OFF after checking.
7-Segment display and check code
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary code
for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Rotary switch setting
value
Indication
LED
SW01
SW02
SW03
1
1
1
Outdoor unit check code
A
Outdoor unit number
(U1)
B
Check code display*
Check code
Check code name
Indication on 7-segment display on the outdoor unit
Auxiliary code
E06
Number of indoor units which received normally
Decrease of number of indoor units
E07
—
Indoor / Outdoor communication circuit error
E08
Duplicated indoor addresses
Duplication of indoor addresses
E15
—
No indoor unit during automatic addressing
E16
00: Capacity over 01 or more: No. of connected units Number of connected capacity over / indoor units
E20
01: Other line outdoor connected
02: Other line indoor connected
Other line connected during automatic addressing
E31
IPDU quantity information*1
IPDU communication error
F04
—
TD sensor error
F06
—
TE sensor error
F07
—
TL sensor error
F08
—
TO sensor error
F12
—
TS sensor error
F13
—
TH sensor (Board installed) error
F15
—
Outdoor temp. sensor miswiring (TE, TL)
F16
—
Outdoor pressure sensor miswiring (Pd, Ps)
F23
—
Ps sensor error
F24
—
Pd sensor error
F31
—
Outdoor EEPROM error
H01
—
Compressor breakdown
D600
A
B
D601 D602 D603 D604
H02
—
Compressor trouble (Lock)
H03
—
Current detective circuit system error
H06
—
Low-pressure protective operation
L04
—
Outdoor system address duplicated
L06
Number of indoor units with priority
Duplication of indoor units with priority
L08
—
Indoor group / Address unset
L10
—
Outdoor capacity unset
L29
IPDU quantity information *1
IPDU quantity error
L30
Detected indoor unit address
External interlock of indoor unit
P03
—
Discharge temp TD error
P04
—
High-pressure switch error
P05
00
Phase missing detection
*E (*: Fan motor number)
Fan motor Vdc error
—
Compressor Vdc error
P07
—
Heat sink overheat error
P10
Detected indoor unit address
Indoor overflow error
P13
—
Outdoor liquid back detection error
P15
01: TS condition 02: TD condition
Gas leak detection
P19
—
4-way valve operation error
P20
—
High-pressure protective operation
P22
*0: Elemental device short
*1: Position detective circuit error
*2: Input current sensor error
*3: Fan motor lock error *4: Motor current error
*5: Synchronize, step out error
*C: Sensor temperature error (No TH sensor)
*D: Sensor short, free error (No TH sensor)
(*: Fan motor number)
Outdoor fan IPDU error
P26
—
G-TR short protection error
P29
—
Compressor position detective circuit system error
*1 IPDU number information
01: Compressor 02: Fan 1 03: Compressor and Fan 1
04: Fan 2 05: Compressor and Fan 2 06: Fan 1 and Fan 2
07: Compressor, Fan 1 and Fan 2 08: Fan 3 09: Compressor and Fan 3
0A: Fan 1 and Fan 3 0B: Compressor, Fan 1 and Fan 3 0C: Fan 2 and Fan 3
0D: Compressor, Fan 2 and Fan 3 0E: Fan 1, Fan 2 and Fan 3
0F: Compressor, Fan 1, Fan 2 and Fan 3
Check code
Check code name
Indication on 7-segment display on the outdoor unit
Auxiliary code