Toshiba
– 3 –
LN INTERFACE
Installation Manual
2
Introduction
Applicable air conditioners
TCC-LINK compatible air conditioners
Applications / functions / features
Applications
The LN interface is used to control TCC-LINK compatible TOSHIBA / Carrier air conditioners by the building control
system using LON (Local Operating Network).
Functions
The LN interface converts signals between TCC-LINK signals for air conditioners and L
ON
W
ORKS
®
signals.
Features
The LN interface enables various settings such as air conditioner operation stop, temperature, operation mode
switching by the building control system, as well as monitoring of operating status, room temperature, various
settings, etc.
One LN interface has a capacity to control indoor units of up to 64 units.
A free topology FT-X1 transceiver is used as the L
ON
W
ORKS
®
transceiver (also communicatable with FTT-10A).
Specifications
External view
Unit: inch (mm)
Name
LN interface
Model
TCB-IFLN642TLUL
Power supply
120 VAC, 60 Hz
Power consumption
5 W
Number of connectable indoor units
64 units
Operating temperature / humidity
32 to 104 °F (0 to 40 °C), 10 to 90% RH (no condensation)
Storage temperature
-4 to 140 °F (-20 to +60 °C)
Dimensions
2.59” (H) x 7.59” (W) x 9.68” (D) inch (66 (H) x 193 (W) x 246 (D) mm)
Mass
2.98 lb (1.35 kg)
7.59" (193)
3.03" (77)
9.68" (246)
9.68" (246)
2.5"
(63.6)
2.59" (66)
3.03" (77)
7.6" (193.4)
8.62" (219)
9.21" (234)
7.59" (193)
6-Ø7/32”
(6-Ø5.5)
mounting holes
3-EN