E6581371
c
5. Specifications
< Environmental specification >
Item Specification
Service environment
Conforms to VF-FS1
Operation temperature
Conforms to VF-FS1
Storage temperature
-25 to +65
℃
Relative humidity
20 to 93% (free from condensation and vapor)
Vibration 5.9m/s
2
(0.6G) or less (10 to 55 Hz) (To be complied with JIS C0040.)
< L
ON
W
ORKS
communication option (LIU007Z) side >
Item Specification
Note
Applicable
model
Only one board connection is
available.
VF-FS1
Communication
method
MODBUS-RTU
Baud rate
19200bps
Commun
ication
between
inverter
Set the inverter parameter
(refer to section 3.2)
Parity Even
number
Control power supply
5 V
Supplied from inverter
DC
2 circuits (F,R)
Logic input terminal
Slide switch (SW1) enable to select
logical configurations (Source/Sink).
Not isolated
Logic output terminal
Nothing
1 circuit (FL): 30V
-0.5A
DC
Relay contact output
terminal
250V -1A (cos
φ
=1
)
Isolated
AC
250V -0.5A (cos
φ
=0.4)
AC
(R
1 circuit (VIB):
10V
DC
IN
=
30kohm)
Not isolated
Analog input terminals
Analog output terminals
Nothing
Power supply output
24V
-50mA
Current limit function
DC
< Network side >
Item Specification
Notes
Transceiver
TP/FT-10 type
78kbps
Channel type
(Free topology transceiver
ANSI/EIA/CEA 709.3
Communication signal
2 wires plus shield
NETA, SHLD, NETB
Transmission distance
Between devices: 400m at maximum
When recommended cable is used:
(Free topology)
Total cable length: 500m at maximum
Level 4/22AWG
Total cable length: 1400m at
maximum
Transmission distance
When recommended cable is used:
(Bus topology)
Level 4/22AWG
Stub length: 3m at maximum
Because a host and routers are
counted as one board, the option can
be connected up to 63 nodes.
Number of connected
nodes
Free topology 63 nodes at maximum
Protocol LonTalk
ANSI/EIA
709.1
Number of domains: 2
Address and related
items
Number of address entries: 37
Number of alias tables: 8
Number of transmission data: 17
L
ON
M
ARK
Variable Speed Motor
Drive functional profile.
Network variables
Number of receiving data: 8
Number of configuration property: 12
Used for notification of Neuron ID to
the host.
Service pin
Mechanical switch (SW2)
Applicable terminal block
Terminal block
Detachable terminal block 3-pole
Manufacturer: PHOENIX CONTACT
Type-Form : MSTB 2,5/3-ST-5.08