PRE-OPERATION SET-UP
CONTROLS
The drive unit for the closing coil assembly is installed in a cavity in the molded frame housing. The
closing circuit can be operated by applying either AC or DC to this drive unit. The optional latch trip
circuit uses DC as standard. When a latched contactor is operated using AC power, it is
recommended that a capacitor trip device be used.
The standard control voltage (factory preset) is 120V AC. To operate at other ratings see the
selection chart below.
Fig. 2 Control Voltage Selection for Closing Coils
The following is a list of the available trip coil voltages for a latched type contactor:
24 V DC
32 V DC
48 V DC
125 V DC
250 V DC