GX9 ASD Installation and Operation Manual
I/O and Control
The
GX9 ASD
can be controlled by several input types and combinations thereof, as well as operate
within a wide range of output frequency and voltage levels. This section discusses the ASD control
methods and supported I/O functions.
The
Terminal Board
supports discrete and analog I/O functions and is shown in
lists the names and the default settings of the input and output terminals of the
Terminal Board
.
See the section titled
Terminal Descriptions on pg. 21
for an expanded description of each terminal.
Note:
Set the
Command Mode
to
Terminal Board
to use the input control lines of the
Terminal Board
for command input (Program
Fundamental
Standard Mode
Selection
Command Mode
Terminal Board). Output lines of the
Terminal
Board
need not be selected to enable the output. However, output lines will have to be
set to a specific function (see
shows the typical connection diagram for the GX9 ASD system.
Table 2. Terminal Board Terminal Names and Functions.
Default Term.
Setting
Input/Output
Default Function
(also see
Terminal Descriptions on pg. 21
)
Circuit Config.
ST
Discrete Input
Connect to CC
to activate
(Sink mode)
Sink/Source
switching
applies to
discrete input
terminals only.
Standby
— Multifunctional programmable discrete input. Activation
required for normal ASD operation.
RES
Reset
— Multifunctional programmable discrete input. Resets a faulted
ASD.
F
Forward
— Multifunctional programmable discrete input.
R
Reverse
— Multifunctional programmable discrete input.
S1
Preset Speed 1
— Multifunctional programmable discrete input.
S2
Preset Speed 2
— Multifunctional programmable discrete input.
S3
Preset Speed 3
— Multifunctional programmable discrete input.
S4
Emergency Off
— Multifunctional programmable discrete input.
RR
Analog Input
RR
— Multifunction programmable analog input
(0.0 to 10 volt input — 0 to 80 Hz output).
RX
RX
— Multifunctional programmable analog input
(-10 to +10 VDC input — -80 to +80 Hz output).
II
II
— Multifunctional programmable analog input (4 [0] to 20 mADC
input — 0 to 80 Hz output). Return at II(-).
VI
VI
— Multifunctional programmable analog input
(0 to 10 VDC input — 0 to 80 Hz output).
AM
Analog Output
Produces an output current that is proportional to the magnitude of the
function assigned to this terminal.
FM
OUT1 (C-A)
Switched
Output
Low Frequency
— Programmable contact (N.O.).
OUT2 (C-A)
Reach Frequency
— Programmable contact (N.O.).
FLA
Fault relay (N.O.).
FLB
Fault relay (N.C.).
FLC
Fault relay (Common).
FP
Pulsed Output
Frequency Pulse
— an output pulse train that has a frequency which is
based on the output frequency of the ASD.
P24
DC Output
24 VDC @ 50 mA output.
PP
PP
— 10.0 VDC voltage source for the external potentiometer.
CC
—
Return for analog and discrete input terminals.
DO NOT
connect to
Earth Gnd.
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......