18
GX9 ASD Installation and Operation Manual
Power Connection Requirements
Connect the 3-phase input power of the correct voltage to the input terminals of the ASD at
R/L1
,
S/L2
,
and
T/L3
(see
for the typical electrical connection scheme and
for the terminal
locations).
Connect the output of the ASD to the motor from the ASD terminals
U/T1
,
V/T2
, and
W/T3
. The input
and output conductors and terminal lugs used shall be in accordance with the requirements listed in the
section titled
Voltage/Current Specifications on pg. 237
.
Install a molded case circuit breaker (MCCB) or fuse between the 3-phase power source and the ASD in
accordance with the fault current setting of the ASD and the
NEC
Article 430
.
The ASD is designed and tested to comply with UL Standard 508C. Modifications to the ASD system
may disqualify the UL rating.
As a minimum, the installation of the ASD shall conform to the
NEC
Article 110
, the
Occupational
Safety and Health Administration
requirements, and to any other local and regional industry codes
and standards.
Note:
In the event that the motor rotates in the wrong direction when powered up, reverse
any two of the three ASD output power leads (U, V, or W) connected to the motor.
Figure 4. The GX9 ASD/Motor Typical Connection Diagram.
CAUTION
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......