GX9 ASD Installation and Operation Manual
15
Installation and Connections
The
GX9 ASD
may be set up initially by performing a few simple configuration settings. To operate
properly, the ASD must be securely mounted and connected to a power source (3-phase AC input at the
L1/R
,
L2/S
, and
L3/T
terminals). The control terminals of the ASD may be used by connecting the
terminals of the
Terminal Board
(P/N 48570) to the proper sensors or signal input sources (see the
section titled
Note:
The optional
ASD-Multicom
boards
may be used to expand the I/O functionality of
the ASD. See the section titled
GX9 ASD Optional Devices on pg. 245
for more
information on the available options.
The output terminals of the ASD (T1/U, T2/V, and T3/W) must be connected to the motor that is to be
controlled (see
).
As a minimum, the installation of the ASD shall conform to
Article 110
of the
NEC
, the
Occupational
Safety
and
Health Administration
requirements, and to any other local and regional industry codes
and standards.
The
Startup Wizard
assists with the initial configuration of the commonly used GX9 ASD parameters.
See the section titled
for additional information on the
Startup Wizard
. The
Startup Wizard
is launched by configuring the system to start the wizard automatically upon a system
restart.
Installation Notes
Do Not
apply commercial power to the output terminals
T1/U
,
T2/V
, or
T3/W
.
If an output contactor is used for bypass operation, it must be interlocked such that commercial power is
never applied to the output terminals of the ASD (T1/U, T2/V, or T3/W).
If a secondary magnetic contactor
(MC) is used between the output of the ASD and the motor, it should
be interlocked such that the
ST – CC
connection is disconnected before the output contactor is opened.
Do Not
open and then close a secondary magnetic contactor between the ASD and the motor unless the
ASD is off and the motor is not rotating.
Note:
Re-application of power via a secondary contact while the ASD is on or while the
motor is still turning may cause ASD damage.
Disconnect the ASD from the motor before megging or applying a bypass voltage to the motor.
When a brake-equipped motor is connected to the ASD, it is possible that the brake may not release at
startup because of insufficient voltage. To avoid this,
Do Not
connect the brake or the brake contactor to
the output of the ASD.
The
ST
-to-
CC
connection is further enhanced by the operation of the
MS1 AUX
relay circuit. The
MS1
AUX
relay circuit is normally open and closes the
ST
-to-
CC
connection (via ST1) only after normal
system power is available. The
MS1 AUX
relay circuit prohibits the
ST
-to-
CC
connection in the event
that the
MS1
contactor fails to close during start up or if
MS1
opens while the ASD is running.
CAUTION
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......