GX9 ASD Installation and Operation Manual
Regenerative Braking Torque Limit 2 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F445
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 3 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F446
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 3 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F447
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 4 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper limit for the #4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F448
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 4 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper limit for the #4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F449
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Torque Limit Mode
Program
Torque
Torque Limit Settings
Contact Toshiba’s Marketing Department for information on this parameter.
Settings:
0 — Power Running/Regenerative Torque Limit
1 — Positive/Negative Torque Limits
Direct Access Number — F450
Parameter Type —
Selection List
Factory Default —
Power Running/
Regenerative Torque Limit
Changeable During Run —
No
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......