GX9 ASD Installation and Operation Manual
101
Motor Overload Protection Level 3
Program
Motor
Motor Set 3
The
Motor Overload Protection Level 3
parameter specifies the motor
overload current level for
Motor Set
3. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to
Amps
(A/V) or it
may be set as a percentage of the ASD rating. The nameplated FLA of the
motor may be entered directly when
Amps
is selected as the unit of
to change the display unit).
The
Motor 3 Overload Protection Level
setting
will be displayed in
Amps
if
the
EOI
display units are set to
A/V
rather than
%
.
Direct Access Number
— F177
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 10.00
Maximum — 100.00
Units — %
Base Frequency 4
Program
Motor
Motor Set 4
The
Base Frequency 4
setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The
Base Frequency Voltage 4
parameter is set at
This parameter is used only when the parameters for
Motor Set
4
are
configured and selected.
Motor Set
4
may be selected by a properly configured
input terminal (see
For proper motor operation, the
Base Frequency
should be set for the
nameplated frequency of the motor.
Direct Access Number — F178
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Base Frequency Voltage 4
Program
Motor
Motor Set 4
The
Base Frequency Voltage 4
is the
Motor
4
output voltage at the
Base
Frequency
4
). Regardless of the programmed value, the output voltage
cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Correction
setting (
).
This parameter is used only when the parameters for
Motor Set
4
are
configured and selected.
Motor Set
4
may be selected by a properly configured
input terminal (see
Direct Access Number — F179
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 700.0
Units — Volts
Manual Torque Boost 4
Program
Motor
Motor Set 4
The
Manual Torque Boost 4
function
is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the
Base Frequency
4
setting
See parameter
(Manual Torque Boost 1) for an explanation of torque
boost.
This parameter is used only when the parameters for
Motor Set
4
are
configured and selected.
Motor Set
4 may be selected by a properly configured
input terminal (see
Direct Access Number — F180
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......