GX9 ASD Installation and Operation Manual
UP/DOWN Frequency Disposition at Power Down
Program
Frequency
UP/DOWN Frequency Settings
When the
Frequency Mode 1 Selection
(
) setting is set to
UP/DOWN
Frequency
, this parameter determines the outcome of the
Frequency Mode 1
(frequency) setting when the ASD is powered down, stopped, or tripped.
Settings:
0 — Erase
1 — Store
If
Erase
is selected, the ASD will
not
store the frequency setpoint and
establishes a setpoint of 0.0 Hz when restarted.
If
Store
is selected, the ASD will retain the ending frequency setpoint in
memory at the power down, stop, or trip. This setpoint will be used as the initial
frequency setpoint when the ASD is restarted.
An activated discrete input terminal configured as
UP/DOWN Frequency
(clear) will establish a frequency setpoint of 0.0 Hz regardless of the
UP/
DOWN Frequency Disposition at Power Down
setting (
)
upon restart.
If running with an activated
UP/DOWN Frequency
(up or down) terminal,
activation of the
UP/DOWN Frequency
(clear) terminal forces the ASD output
to the
Lower Limit Frequency
) setting.
UP/DOWN Frequency Function
The
UP/DOWN Frequency
function allows for an externally-supplied discrete
input signal to increase or decrease the output frequency of the ASD.
This method uses the discrete input terminal settings
UP/DOWN Frequency
(up)
,
UP/DOWN Frequency (down)
, and
UP/DOWN Frequency (clear)
.
Activation of the
Up
or
Down
terminals increases or decreases the output
frequency for the duration of the activation at the
Accel 1
or
Decel 1
rates,
respectively.
To activate-and-hold either terminal will continue the up or down function until
reaching the
Upper-Limit Frequency
or the
Lower-Limit Frequency
,
respectively. At which point further activation will be ignored. The
UP/DOWN
Frequency (clear)
function will clear the stored frequency value if stopped or
command the ASD to output the
Lower Limit Frequency
if activated while
running.
Setup Requirements
Command
control source to
Terminal Board
.
Frequency Mode 1
control source to
UP/DOWN
Frequency
.
Set an unused discrete input terminal to
UP/DOWN Frequency (up)
.
Set an unused discrete input terminal to
UP/DOWN Frequency (down)
.
Set an unused discrete input terminal to
UP/DOWN Frequency (clear)
.
Select the outcome of the
Frequency Mode 1
setting when the ASD
is powered down, stopped, or tripped.
Direct Access Number — F108
Parameter Type —
Selection List
Factory Default —
Erase
Changeable During Run —
No
Up/Down Frequency (up) Mode
Up/Down Frequency (down) Mode
Summary of Contents for GX9
Page 2: ......
Page 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Page 4: ......
Page 12: ...iv GX9 ASD Installation and Operation Manual ...
Page 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Page 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Page 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Page 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Page 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Page 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Page 268: ......
Page 269: ......