36
GX7R ASD Quick Start Guide
Panel Menu
The
Panel
menu is accessed by pressing
ESC
from the
screen. The control settings
of the
Panel
menu are effective for EOI control only.
The
Panel
menu provides quick access to the following menu parameters:
Direction
—
Forward
or
Reverse
.
Stop Pattern
— The
Decel Stop
or
Coast
Stop
selection
determines the method used to stop the
motor when using the
Stop|Reset
key of the EOI. The
Decel Stop
setting enables the
Dynamic
Braking
system setup at
F304
or the
DC Injection Braking
system setup at
F250
,
F251
, and
F252
.
The
Coast Stop
setting allows the motor to stop at the rate allowed by the inertia of the load.
Note:
Dynamic Braking
is not used with the GX7R ASD.
Note:
The
Stop Pattern
setting has no effect on the
Emergency Off
settings of
F603
.
V/f Group
— One of four
V/f
profiles may be selected and run. Each
V/f
profile is comprised of four
user settings:
Base Frequency
,
Base Frequency Voltage
,
Manual Torque Boost
, and
Electronic
Thermal Protection
. Expanded descriptions of these parameters may be found in the
GX7R ASD
Install and Op Manual
.
Accel/Decel Group
— One of four
Accel/Decel
profiles may be selected and run. Each of the
Accel/Decel
profiles is comprised of three user settings:
Acceleration
,
Deceleration
, and
Pattern
.
Expanded descriptions of these parameters may be found in the
GX7R ASD Install and Op Manual
.
Feedback in Panel Mode
— This feature enables or disables the
PID
feedback function.
Torque Limit Group
— This parameter is used to select one of four preset positive torque limits to
apply to the active motor (of a multiple motor configuration). The settings of profiles 1 – 4 may be
setup at
F441
,
F444
,
F446
, and
F448
, respectively.
Summary of Contents for GX7R ASD
Page 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Page 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Page 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...