6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 914 -
5.3.2
Configuration switch
The CPU module has a jumper to change configuration mode (Jumper W6). Figure 5.3-3 shows
the location. For default mode (normal), Pins 1-2 and 3-4 are open (i.e., default configuration
has been set by the manufacture in accordance with the order code). When the user wishes to
alter the other mode particularly, close either Pin 1-2 or Pin 3-4 using a jumper (Optional EP-
221).
COM#2
CPM2
COM#1
CPU
COM#3
COM#4
COM#5
W5
2-1
4-3
W8
2-1
4-3
W6
(1-2)
W6
(3-4)
Jumper
Configuration mode
Open
Open
Default (normal) mode(i.e.,
manufacture setting mode )
Closed
Open
Constrained mode (1A rated)
Open
Closed
Constrained mode (5A rated)
CPU
2-1
4-3
2-1
4-3
2-1
4-3
W6
2-1
4-3
W7
2-1
4-3
Figure 5.3-3 Configuration switch
Note: Alter the configuration mode before VCT setting. Using GR-TIEMS, the user
needs to rewrite the settings. See
Chapter Installation and setting: Changing
rated current for more detail.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......