6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 735 -
Table 4.8-5 Mapping points for the reception of control commands
Signal Number
Signal Name
Description
M/O
512001 7003016D08
DEV01_CONTROL_REQ
DPOS01 control command received. (Mapping Data)
M
512001 7003026D08
DEV02_CONTROL_REQ
DPOS02 control command received. (Mapping Data)
M
512001 7003036D08
DEV03_CONTROL_REQ
DPOS03 control command received. (Mapping Data)
M
…
…
…
512001 7003486D08
DEV72_CONTROL_REQ
DPOS72 control command received. (Mapping Data)
M
Table 4.8-6 Input signals to condition logic
Signal Number
Signal Name
Description
M/O
522001 000A011001
CBK_STATE
Command Blocking status ( Off / Blocked)
N/A
523001 000D001F40
ASEQ_MULTI_SEL
Automatic sequence control is in progress.
N/A
5A0001 0008001F41
DCB RCV OR
Double Command Blocking(DCB) is in progress.
N/A
5A0001 0008001F40
Travelling OR
Travelling events are detected.
N/A
4A0001 8300001B6F
GEN.TRIP
General trip
N/A
5A0001 3108003F40
SDCEN
(This is setting of CMNCTRL)
N/A
5A0101 3100001F43
SERI_ERR
Serious Error detected
N/A
Table 4.8-7 PLC Connection points (Input signals for select condition logic)
Signal Number
Signal Name
Description
M/O
512001 810301EE62
DPOS01IN_TMP_32
DPOS01 additional failure condition(PLC#1)
O
512001 810302EE62
DPOS02IN_TMP_32
DPOS02 additional failure condition(PLC#1)
O
512001 810303EE62
DPOS03IN_TMP_32
DPOS03 additional failure condition(PLC#1)
O
….
….
….
5A0101 801016EF40
DPOS72IN_TMP_32
DPOS72 additional failure condition(PLC#1)
O
512001 800301EE61
DPOS01IN_TMP_31
DPOS01 user configurable select condition(PLC#2)
O
512001 800302EE61
DPOS02IN_TMP_31
DPOS02 user configurable select condition(PLC#2)
O
512001 800303EE61
DPOS03IN_TMP_31
DPOS03 user configurable select condition(PLC#2)
O
…
…
…
512001 800348EE61
DPOS72IN_TMP_31
DPOS72 user configurable select condition(PLC#2)
O
512001 820301ED50
DPOS01IN_TMP_28
DPOS01 control hierarchy condition(PLC#3)
M
512001 820302ED50
DPOS02IN_TMP_28
DPOS02 control hierarchy condition(PLC#3)
M
512001 820303ED50
DPOS03IN_TMP_28
DPOS03 control hierarchy condition(PLC#3)
M
….
….
….
512001 820348ED50
DPOS04IN_TMP_28
DPOS20 control hierarchy condition(PLC#3)
M
Table 4.8-8 PLC Monitoring points (Output signal for select condition logic)
Signal Number
Signal Name
Description
512001 8003011F5A
DPOS01_SC_ST_ERR
DPOS01 select command mode is invalid.
512001 8003021F5A
DPOS02_SC_ST_ERR
DPOS02 select command mode is invalid.
512001 8003031F5A
DPOS03_SC_ST_ERR
DPOS03 select command mode is invalid.
….
….
….
512001 8003481F5A
DPOS72_SC_ST_ERR
DPOS72 select command mode is invalid.
512001 8103011F5F
DPOS01_F_QLT_SPP
Event suppression detected (DPOS01)
512001 8103021F5F
DPOS02_F_QLT_SPP
Event suppression detected (DPOS02)
512001 8103031F5F
DPOS03_F_QLT_SPP
Event suppression detected (DPOS03)
….
….
….
512001 8103481F5F
DPOS72_F_QLT_SPP
Event suppression detected (DPOS72)
512001 8203011F60
DPOS01_F_BI_ERR
BI connection error detected(DPOS01)
512001 8203021F60
DPOS02_F_BI_ERR
BI connection error detected(DPOS02)
512001 8203031F60
DPOS03_F_BI_ERR
BI connection error detected(DPOS03)
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......